2. SELECTING THE INSTALLATION SITE

2-1. Indoor Unit

AVOID:
G
areas where leakage of flammable gas may be
expected.
G
places where large amounts of oil mist exist.
G
direct sunlight.
G
locations near heat sources which may affect the
performance of the unit.
G
locations where external air may enter the room
directly. This may cause "sweating" on the air dis-
charge ports, causing them to spray or drip.
G
locations where the remote controller will be splashed
with water or affected by dampness or humidity.
G
installing the remote controller behind curtains or
furniture.
G
locations where high-frequency emissions are
generated.
DO:
G
select an appropriate position from which every
corner of the room can be uniformly cooled.
G
select a location where the ceiling is strong enough
to support the weight of the unit.
G
select a location where tubing and drain pipe have
the shortest run to the outdoor unit.
G
allow room for operation and maintenance as well as
unrestricted air flow around the unit.
G
install the unit within the maximum elevation
difference above or below the outdoor unit and within
a total tubing length (L) from the outdoor unit as
detailed in Table 1-16.
G
allow room for mounting the remote controller about
3 ft. off the floor, in an area that is not in direct
sunlight nor in the flow of cool air from the indoor
unit.
NOTE
Air delivery will be degraded if the distance from the
floor to the ceiling is greater than 10 ft.
Ceiling-Mounted Type
min. 10 in.
NOTE
The rear of the indoor unit can be installed flush
against the wall.
Air
discharge
min. 2 ft.
Concealed Duct (High-Static Pressure) Type
4-Way Air Discharge Semi-Concealed Type
1-Way Air Discharge Semi-Concealed Type
Ceiling
min. 2 in.
Obstacle
Wall-Mounted Type
min.
6 in.
17
Ceiling
Wall
min. 10 in.
Front view
Air intake
Side view
Max. 10 in.
Obstacle
Fig. 2-1
Fig. 2-2
Air
discharge
Air
intake
Wall
min. 2 in.
Side view
Fig. 2-3
min. 6 in.
min.
6 in.
Front View
Fig. 2-4
Wall