Check Of Limit Density; Installing Distribution Joint - Sanyo Mini ECO-i 85464359981002 Installation Instructions Manual

Sanyo air conditioner installation instructions
Table of Contents

Advertisement

Always check the gas density
WARNING
limit for the room in which the
unit is installed.

1-10. Check of Limit Density

When installing an air conditioner in a room, it is neces-
sary to ensure that even if the refrigerant gas accidentally
leaks out, its density does not exceed the limit level for
that room.
If the density could exceed the limit level, it is necessary to
provide an opening between the unit and the adjacent
room, or to install mechanical ventilation which is inter-
locked with the leak detector.
(Total refrigerant charged amount: oz)
(Min. indoor volume where the indoor unit is installed: ft.
< Limit density 0.3 (oz/ft.
The limit density of refrigerant which is used in this unit is
3
0.3 oz/ft.
(ISO 5149).
The shipped outdoor unit comes charged with the amount
of refrigerant fixed for each type, so add it to the amount
that is charged in the field. (For the refrigerant charge
amount at shipment, refer to the unit's nameplate.)
Pay special attention to any
CAUTION
location, such as a basement,
etc., where leaking refrigerant
can accumulate, since refrig-
erant gas is heavier than air.

1-11. Installing Distribution Joint

(1) Refer to "HOW TO ATTACH DISTRIBUTION JOINT"
enclosed with the optional distribution joint kit
(APR-P160BA).
(2) In order to prevent accumulation of refrigerant oil in
stopped units, if the main tubing is horizontal then each
branch tubing length should be at an angle that is
greater than horizontal. If the main tubing is vertical,
provide a raised starting portion for each branch.
(3) If there are height differences between indoor units or if
branch tubing that follows a distribution joint is connect-
ed to only 1 unit, a trap or ball valve must be added to
that distribution joint. (When adding the ball valve,
locate it within 1.3 ft. of the distribution joint.)
(Consult with SANYO separately concerning the ball
valve.)
If a trap or ball valve is not added, do not operate
the system before repairs to a malfunctioning unit
are completed. (The refrigerant oil sent through the
tubing to the malfunctioning unit will accumulate
and may damage the compressor.)
Minimum indoor volume & floor area as against the
amount of refrigerant is roughly as given in the following
table.
)
3
)
3
(BV: purchased
Main tubing
13
3
ft.
10000
9500
9000
Range below
8500
the density limit of
8000
3
0.3 oz/ft.
7500
(countermeasures
7000
6500
not needed)
6000
5500
5000
4500
4000
3500
3000
Range above
2500
the density limit of
2000
0.3 oz/ft.
1500
(countermeasures
1000
500
needed)
0
0
500
1000
1500 2000 2500 3000
Total amount of refrigerant
Tube branching methods (horizontal use)
A
B
Arrow view
Types of vertical trap specifications
(When using ball valve)
Main tubing
Indoor unit (more than 2 units)
Ball valve
(If only 1 unit is connected,
a ball valve is also needed on this side.)
separately)
Indoor unit (1)
(When not using ball valve)
Horizontal
Indoor unit
Branch tubing is
directed upward.
More than
8 in.
Indoor unit is directed downward
2
ft.
1136
1079
1022
966
909
852
795
738
682
625
568
511
454
398
341
284
227
3
170
114
57
0
oz
B
Horizontal
A
line
View as seen
from arrow
(Each unit is connected to
tubing that is either level
or is directed downward.)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents