Danfoss MCA 124 Operating Instructions Manual page 55

Table of Contents

Advertisement

Warnings and Alarms
Bit
Hex
0
00000001
1
00000002
2
00000004
3
00000008
4
00000010
5
00000020
6
00000040
7
00000080
8
00000100
9
00000200
10
00000400
11
00000800
12
00001000
13
00002000
14
00004000
15
00008000
16
00010000
17
00020000
18
00040000
19
00080000
11
11
20
00100000
21
00200000
22
00400000
23
00800000
24
01000000
25
02000000
26
04000000
27
08000000
28
10000000
29
20000000
30
40000000
31
80000000
Table 11.3 Description of Alarm Word, Warning Word and Extended Status Word
The alarm words, warning words and extended status
words can be read out via serial bus or optional fieldbus
for diagnose. See also 16-94 Ext. Status Word.
54
MCA 124 EtherCAT Operating Instruction
Dec
Alarm Word
1
Brake Check
2
Pwr. Card Temp
4
Earth Fault
8
Ctrl.Card Temp
16
Ctrl. Word TO
32
Over Current
64
Torque Limit
128
Motor Th Over
256
Motor ETR Over
512
Inverter Overld.
1024
DC under Volt
2048
DC over Volt
4096
Short Circuit
8192
Inrush Fault
16384
Mains ph. Loss
32768
AMA Not OK
65536
Live Zero Error
131072
Internal Fault
262144
Brake Overload
524288
U phase Loss
1048576
V phase Loss
2097152
W phase Loss
4194304
Fieldbus Fault
8388608
24 V Supply Low
16777216
Mains Failure
33554432
1.8 V Supply Low
67108864
Brake Resistor
134217728
Brake IGBT
268435456
Option Change
536870912
Drive Initialized
1073741824
Safe Stop (A68)
2147483648
Mech. brake low
MG92A302 - VLT
Alarm Word 2
Warning Word
ServiceTrip,
Brake Check
Read/Write
ServiceTrip,
Pwr. Card Temp
(reserved)
ServiceTrip,
Earth Fault
Typecode/
Sparepart
ServiceTrip,
Ctrl.Card Temp
(reserved)
ServiceTrip,
Ctrl. Word TO
(reserved)
Over Current
Torque Limit
Motor Th Over
Motor ETR Over
Inverter Overld.
DC under Volt
DC over Volt
DC Voltage Low
DC Voltage High
Mains ph. Loss
No Motor
Live Zero Error
KTY error
10V Low
Fans error
Brake Overload
ECB error
Brake Resistor
Brake IGBT
Speed Limit
Fieldbus Fault
24V Supply Low
Mains Failure
Current Limit
Low Temp
Voltage Limit
Encoder loss
Output freq. lim.
PTC 1 Safe Stop
Safe Stop (W68)
(A71)
Dangerous
Extended Status Word
Failure (A72)
®
is a registered Danfoss trademark
Warning
Extended
Word 2
Status Word
Ramping
AMA Running
Start CW/CCW
Slow Down
Catch Up
Feedback High
Feedback Low
Output Current
High
Output Current Low
Output Freq High
Output Freq Low
Brake Check OK
Braking Max
Braking
Out of Speed Range
OVC Active
AC Brake
KTY Warn
Password Timelock
Fans Warn Password Protection
ECB Warn
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused
PTC 1 Safe
Unused
Stop (W71)
Unused

Hide quick links: