Danfoss MCA 124 Operating Instructions Manual page 40

Table of Contents

Advertisement

Parameters
12-59 EtherCAT Status
Range:
Function:
Bit
0
31
Table 8.1 Bit Interpretation
8.3.5 12-8* Other Ethernet Services
12-80 FTP Server
Option:
Function:
[0]
Disabled
Disables the built-in FTP server.
*
[1]
Enabled
Enables the built-in FTP server.
12-81 HTTP Server
Option:
Function:
[0]
Disabled
Disables the built-in HTTP (web) server.
*
[1]
Enabled
Enables the built-in HTTP (web) server.
12-82 SMTP Service
Option:
Function:
[0]
Disabled Disables the SMTP (e-mail) service on the option.
*
[1]
Enabled
Enables the SMTP (e-mail) service on the option.
12-89 Transparent Socket Channel Port
Range:
Function:
Size
[
0 -
Configures the TCP port number for the
related
0. ]
transparent socket channel. This configu-
*
ration enables FC telegrams to be sent
transparently on Ethernet via TCP. Default
value is 4000, 0 means disabled. The MCT
10 Set-up Software uses this port.
8.3.6 12-9* Advanced Ethernet Settings
12-90 Cable Diagnostic
Option:
Function:
Enables/disables advanced Cable diagnosis
function. If enabled, the distance to cable errors
can be read out in 12-93 Cable Error Length. The
parameter resumes to the default setting of
Disable after the diagnostics have finished.
[0]
Disabled
*
[1]
Enabled
NOTE
The cable diagnostics function is only issued on ports
where there is no link (see 12-10 Link Status, Link Status)
MCA 124 EtherCAT Operating Instruction
12-91 Auto Cross Over
Option:
1
Meaning
[0]
Reserved
[1]
12-93 Cable Error Length
Range:
0
*
®
MG92A302 - VLT
is a registered Danfoss trademark
Function:
Disabled
Disables the auto cross-over function.
Enabled
Enables the auto cross-over function.
*
Function:
[0 -
If Cable Diagnostics is enabled in 12-90 Cable
65535 ]
Diagnostic, the built-in switch is possible via
Time Domain Reflectometry (TDR). This
measurement technique detects common
cabling problems such as open circuits, short
circuits, and impedance mismatches or breaks in
transmission cables. The distance from the
option to the error is displayed in meters with
an accuracy of +/-2 m. The value 0 means no
errors detected.
8
8
39