DETECT MAINTENANCE REPORT: Press this soft key to print a list from the printer connected to the control panel that contains the
detector maintenance status for each installed addressable detector. The report looks like this:
******DETECTOR MAINTENANCE******************************************************
NORMAL SMOKE(LASER) Detector
Alarm: 000% PreAlarm: 000% A6P6 V000
NORMAL SMOKE ACCLIM Detector
Alarm: 000% PreAlarm: 000% A8P8 V000
Field Identification
Detector Maintenance Report
State
NORMAL SMOKE(LASER) Detector
Alarm: 000% PreAlarm: 000% A6P6 V000
Percent of
alarm
threshold*
* Whichever occupancy value is in effect when the report is printed.
INSTALLED POINTS: Press this soft key to display the Installed Points Menu screen.

5.2 Print Programming Menu Screen

This screen displays when the PROGRAMMING soft key is pressed on the PRINTER FUNCTIONS screen. Refer to Figure 5.1 on
page 47).
Soft Keys
NETWORK PARAMETERS: Press to print node number, node label, Channel A and B threshold, network style. The report looks like
this:
48
L01D001 000330us 000340us Comp:000% Pk: 002%
L01D002 000030us 000000us Comp:000% Pk: 000%
Current reading of raw analog
value in microseconds
Extended
Label
L01D001 000330us 000340us Comp:000% Pk: 002%
Percent of
prealarm
threshold*
Programmed alarm sensitivity*
P R I N T P R O G R A M M I N G M E N U
N E T W O R K P A R A M E T E R S
S E T T I N G S
T I M E R S
Figure 5.2 Print Programming Screen
L01D001
L01D002
Long term average of
raw analog value in
microseconds
Label
L01D001
Verification count
Programmed prealarm sensitivity*
L C D D I S P L A Y
AFP-3030 Operations Manual — P/N DOC-01-033:C 05/12/2018
Print Programming Menu Screen
Compensation
percentage
Detector peak
Address