ATTACHING SOLENOIDS

The NODE-100 is provided with a solenoid attached to the
controller . The NODE-200, NODE-400, and NODE-600 multi-station
controllers will operate up to 2, 4, or 6 solenoids, respectively .
Hunter DC solenoids (P/N 458200) can easily be installed on all
Hunter Plastic Valves .
NOTE: Must use DC Latching Solenoids
operating between 9-11VDC. 24VAC Solenoids
will not operate with the NODE.
Common Wire (Black Leads)
Station Wire (Red Leads)
5

To Wire DC Solenoids to the NODE

1 .
Attach the black leads from each solenoid to the single
common wire (black lead) coming from the NODE . Secure all
wire connections with waterproof connectors .
2 .
Attach one red wire from each solenoid to the corresponding
station wire (red lead) from the NODE . The station numbers
are identified on the face of the NODE . Secure all wire
connections with waterproof connectors .
NOTE: The maximum wire distance between the
solenoid and NODE is 100 ft/30 m (18 gauge
minimum wire size).
ENG