Clearances - Raypak 408 Installation And Operation Manual

Gas-fired pool and spa heater
Table of Contents

Advertisement

5.2. Clearances

5.2.1.
All Heaters
For indoor and outdoors clearances from combustible
surfaces, see the chart below.
Location
Top *
30" (762 mm) Drafthood
Front
Alcove (Open)
Vent
6" (152 mm)
Floor **
0"
Back
6" (152 mm)
Right Side
12" (305 mm) Water Side
Left Side
6" (152 mm) Opposite Water Side
Location
Top *
Unobstructed (Outdoor Stack)
Top ***
36" (76 mm) (Stackless Top)
Right Side
12" (305 mm) Water Side
Left Side
6" (152 mm)
Floor
0"
Back
6" (152 mm)
* Clearance from top of vent terminal
** Do not install on carpeting
*** Clearance from top of heater
Table B.
Minimum Clearances from Combustible Installations
4' (1.2 m)
Minimum
4' (1.2 m)
Minimum
3' (0.9 m)
Minimum
10' (3 m)
Minimum
Forced Air Inlet
Figure 4.
Minimum Distances to Building Openings from
Where Flue Products Exit the Boiler
10
Indoor Installation
Outdoor Installation
4' (1.2 m)
Minimum
1' (0.3 m)
Minimum
Description
a. 3-1/2" (89 mm) thick
masonry walls without
ventilated air space
b. 1/2" (13 mm)insulation
board over 1" (25 mm)
glass fiber or mineral
wool batts
c. 0.024 sheet metal over
1" (25 mm) glass fiber
or mineral wool batts
reinforced with wire on
rear face with ventilated
air space
d. 3-1/2" (89 mm) thick
masonry wall with
ventilated air space
e. 0.024 sheet metal with
ventilated air space
f. 1/2" (13 mm) thick
insulation board with
ventilated air space
g. 0.024 sheet metal with
ventilated air space over
0.024 sheet metal with
ventilated air space.
h. 1" (25 mm) glass fiber
or mineral wool batts
sandwiched between
two sheets 0.024 sheet
metal with ventilated air
space
Derived from National Fuel Gas Code, Table 10.2.3
Table C.
Reduction of Clearances to Protected Surfaces
When installed according to the listed minimum clearances
from combustible construction, the pool heater can still
be serviced without removing permanent construction
around the heater.
However for ease of servicing, we recommend a clearance
of at least 24" (610 mm) in the front, and at least 18" (457
mm) on the water connection side.
Distance
Location
in. (mm)
Back
9 (229)
Right
9 (229)
Left
9 (229)
Vent
5 (127)
Indoor Top
39 (991)
Outdoor Top
Unobstructed
Back
6 (152)
Right
6 (152)
Left
6 (152)
Vent
3 (76)
Indoor Top
30 (762)
Outdoor Top
Unobstructed
Back
4 (102)
Right
4 (102)
Left
4 (102)
Vent
3 (76)
Indoor Top
24 (610)
Outdoor Top
Unobstructed
Back
6 (152)
Right
6 (152)
Left
6 (152)
Vent
6 (152)
Indoor Top
39 (991)
Outdoor Top
Unobstructed
Back
4 (102)
Right
4 (102)
Left
4 (102)
Vent
2 (51)
Indoor Top
24 (610)
Outdoor Top
Unobstructed
Back
4 (102)
Right
4 (102)
Left
4 (102)
Vent
3 (76)
Indoor Top
24 (610)
Outdoor Top
Unobstructed
Back
4 (102)
Right
4 (102)
Left
4 (102)
Vent
3 (76)
Indoor Top
24 (610)
Outdoor Top
Unobstructed
Back
4 (102)
Right
4 (102)
Left
4 (102)
Vent
3 (76)
Indoor Top
24 (610)
Outdoor Top
Unobstructed