The following conditions are displayed in Pool, Spa and
Remote modes.
Display
Thermistor temperatures disagree by
Sensor Failure
more than 2°F (1°C)
Thermistor sensor failed open. Below
Sensor Open
-20°F (-29°C).
Thermistor sensor failed short. Above
Sensor Short
217°F (103°C).
Board is sensing flame when both
Flame w/o CFH
main and pilot valves are commanded
shut.
Pilot gas valve output is not in
PV Output Fault
commanded state.
Main gas valve output is not in
MV Output Fault
commanded state.
Internal Fault
Board fault, replace board.
Memory fault, reset set points,
EEPROM Fault
replace board if fault does not clear.
Time clock/fireman switch circuit is
Clock/Fireman Sw
open.
Low Temp
Water temperature below 36°F (2°C).
Lockout
Table L.
Heat Status Messages - Active Faults
The following conditions are displayed only while there is
a demand for heat present.
Display
Water Sw Open
Water pressure switch open.
Vent/Field
Vent spill switch/field switch #1 open.
Sw #1
Hi Limit 1 Fault
High limit 1 open.
Hi Limit 2 Fault
High limit 2 open.
Rollout Sw Open
Rollout switch open.
Field-supplied flow switch/field switch
Flow/Field SW #2
#2 open.
Alternating with "No pilot sensed" -
Pilot flame not established within the
Ignition Lockout
required time (15 sec or 90 sec).
(Propane Tab
Alternating with "Main Ign Failure"
Broken)
- Pilot flame lost during the 8 second
trial to ignite the main burner.
Ignition Failure
Alternating with "No pilot sensed" -
(Propane Tab Not
Pilot flame not established within 90
Broken)
seconds.
Alternating with "Main Ign Failure"
Ign 6min Delay
- Pilot flame lost 4 times within the 8
(Propane Tab Not
second trial to ignite the main burner.
Broken)
Heater will lockout for 6 minutes
before retrying.
Table M. Heat Status Messages - Demand for Heat
Condition
Condition
8.4.1.
Remote Control Installation and
Operation
CAUTION: Before installing remote controls to the
A
heaters, read the following: The digital thermostat
model is remote-ready in most cases. The digital liquid
crystal display (LCD) shows the actual pool temperature,
operating status, and service codes. See Figure 41. The
touch pad on the control panel allows you to select the
desired pool or spa temperature. It also indicates when
a remote system is controlling the heater by displaying
Remote in the display. When connecting the heater to a
remote system, identify whether it is a two- or three-wire
remote system. Select the appropriate instruction listed
below to properly install the remote to the heater.
8.4.2.
Remote Operation
The heaters are equipped with the ability to work with
external remote controls. The supplied 7-pin remote wiring
connector supplies power out to either a toggle switch or
the switch contacts of a third party remote. The remote
works by either making or breaking the circuit created
by the remote wiring. Typically, a remote does not supply
power to the heater, it only provides a switching function
to turn the heater On or Off. If your remote is supplying
its own voltage to the heater, it will not work with this
heater and may damage the digital circuit board. For
operation of the heater using the onboard thermostatic
controls with a time clock.
Switch" on page 29.
Figure 41. Remote Control Menu - Remote Operation
See "Time Clock/Fireman's
OFF Mode
Heating in the POOL Mode
Heating in the SPA Mode
Remote Mode
27