Installation Instructions - Honeywell Inncom e7 Installation Instructions Manual

Hide thumbs Also See for Inncom e7:

Advertisement

INNCOM e7 Thermostat

Installation Instructions

FOR ALL UNITS IN CARTON. DO NOT THROW AWAY!
CAUTION
Disconnect the power supply before beginning
installation to prevent electrical shock or equipment
damage. All wiring must comply with local codes and
ordinances.
• Read instructions carefully. Failure to follow them could
damage the product or create a hazard.
• Check the ratings given in the instructions and on the product
to make sure the product is suitable for your application.
• Installer must be a trained, experienced service technician.
• After installation is complete, check product operation as
indicated in instructions.
• For variations of these systems, refer to the installation
instructions of the controlled equipment.
INSTALLATION
Location
Select a location about 1.5m (5ft.) above the floor with good air
circulation at average temperature. Do not mount thermostat
where it may be affected by:
• Drafts or dead spots behind doors or in corners.
• Hot or cold air from ducts.
• Radiant heat from sun or appliances.
• Concealed pipes or chimneys.
• Unheated (un-cooled) areas behind the thermostat.
• If RF equipped, do not install near other RF sources/
transmitters.
• When the thermostat is equipped with PIR, consider view
angle, range characteristics, and mounting position for proper
coverage.
Mounting
The INNCOM e7 thermostat is typically mount on a standard
double-gang (4 x 4) junction box. The installation kit provides a
Smart Wall Mounting Plate and an optional Spacer Ring. The
optional Spacer Ring is only required when a standard double-
gang (4 x 4) junction box is not available, or when more space is
required for wiring.
If mounted on a single-gang box, the right side (keypad side) of
the e7 overlaps the wall area to the right. A low-voltage mounting
plate, mud ring, or low-voltage caddy may be used for mounting
24 volt applications.
To mount the e7, complete the following steps:
https://pages1.honeywell.com/e7_Install_Instructions.html
INSTALLATION INSTRUCTIONS
1. Position the optional spacer ring (if used) and Smart Wall
Mounting Plate as shown in Fig. 1.
2. Ensure the optional spacer ring (if used) and Smart
Mounting Plate are oriented with the raised arrow point-
ing UP. Attach them to the junction box using the mount-
ing screws provided.
3. Use wire nuts to connect the Power and HVAC wiring
harness to the power and valve/fan control signal wires
within the electrical box. See the pre-defined commission-
ing document for application-specific wire connections.
4. To connect the unit to the input power and the relays to
the loads, plug the pre-wired power and HVAC signal har-
ness connector into the female receptacle at the back of the
e7 (H1). When using mixed voltage, voltage separation
must be maintained. Line voltage must reside in the left
side of the gang box. Low voltage must reside in the right
side of the gang box.
5. Hook the tabs at the top rear of the e7 housing into the
matching depressions at the top of the Smart Mounting
Plate and rotate the bottom of the housing toward the wall
until it snaps into place.
6. Secure the housing to the Smart Mounting Plate with the
two small captive screws at the bottom of the housing.
7. Apply power to the e7 by closing the applicable supply
breaker. Verify that the e7 powers up. Values should begin
appearing on the LCD display.
4 Junction Box
Optional Spacer Ring
Fig. 1. e7 Exploded View Assembly Reference
Power/HVAC signal
harness to thermostat
Smart Mounting Ring