Operational and basic error limits for thermal resistors
Error limits for thermal resistors
Operational limit (in the entire temperature range, in relation to input range)
•
•
•
Basic error limit (operational limit at 25 °C, in relation to input range)
•
•
•
Operational and basic error limits for thermocouples
Error limits for thermocouples
Operational limit for thermocouples (in the entire temperature range)
Basic error limit for thermocouples (operational limit at 25 °C)
Overall error limits when using internal compensation
•
•
The indicated error limits apply as of the following temperatures:
1
Dimension drawing
See manual ET 200SP BaseUnits
(http://support.automation.siemens.com/WW/view/en/59753521)
Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1)
Manual, 09/2018, A5E32942580-AB
Pt 100, Pt 200, Pt 500, Pt 1000 standard
Pt 100, Pt 200, Pt 500, Pt 1000 climatic
Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000 standard and climatic
Pt 100, Pt 200, Pt 500, Pt 1000 standard
Pt 100, Pt 200, Pt 500, Pt 1000 climatic
Ni 100, Ni 120, Ni 200, Ni 1000 standard and climatic
Operational limit (in the entire temperature range at static thermal state, am-
bient temperature change < 0.3 K/min)
Basic error limit (operational limit at 25 °C at static thermal state, ambient
temperature change < 0.3 K/min)
Thermocouple type T: -200 °C
Thermocouple type K: -100 °C
Thermocouple type B: +700 °C
Thermocouple type N: -150 °C
Thermocouple type E: -150 °C
Thermocouple type R: +200 °C
Thermocouple type S: +100 °C
1
Technical specifications
±1.0 K
± 0.25 K
± 0.4 K
± 0.6 K
± 0.13 K
± 0.2 K
±1.5 K
±1 K
± 2.5 K
±1.5 K
51