Parameters/address space
4.1
Measurement types and measuring ranges
The following table describes the measuring range and the temperature coefficients you can
configure for each measurement type:
Table 4- 1
Measurement types and measuring ranges
Measurement type
Deactivated
Voltage
Resistor (2-wire connection)
Thermal resistor RTD (2-wire connection)
Thermocouple (TC)
For sensors LG-Ni 1000 from Siemens Building Ltd (Landis & Stäfa).
1
Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1)
Manual, 09/2018, A5E32942580-AB
Measuring range
–
±50 mV / ±80 mV /
±250 mV / ±1 V
150 Ω / 300 Ω / 600 Ω /
3 kΩ / 6 kΩ
PTC
Climatic / Standard
Pt 100
Pt 200
Pt 500
Pt 1000
Climatic / Standard
Ni 100
Ni 120
Ni 200
Ni 500
Ni 1000
Climatic
/ Standard
1
1
Ni 1000
Type E, N, J, K, L, S, R,
B, T, C, U, TXK (acc. to GOST)
Temperature coefficient
–
–
-
Pt 0.00385 /
Pt 0.003916 /
Pt 0.003902 /
Pt 0.00392 /
Pt 0.00385055
Ni 0.00618 /
Ni 0.00672
Ni 0.005
-
4