Article number
Power loss
Power loss, typ.
Address area
Address space per module
Address space per module, max.
•
Analog inputs
Number of analog inputs
For voltage measurement
•
For resistance/resistance thermometer
•
measurement
For thermocouple measurement
•
permissible input voltage for voltage input
(destruction limit), max.
Constant measurement current for resistance-
type transmitter, typ.
Cycle time (all channels), min.
Technical unit for temperature measurement
adjustable
Input ranges (rated values), voltages
-1 V to +1 V
•
Input resistance (-1 V to +1 V)
•
-250 mV to +250 mV
•
Input resistance (-250 mV to +250 mV)
•
-50 mV to +50 mV
•
Input resistance (-50 mV to +50 mV)
•
-80 mV to +80 mV
•
Input resistance (-80 mV to +80 mV)
•
Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1)
Manual, 09/2018, A5E32942580-AB
6ES7134-6JF00-0CA1
0.75 W
16 byte; + 1 byte for QI information
8
8
8
8
30 V
2 mA
Sum of the basic conversion times and additional
processing times (depending on the parameteri-
zation of the active channels)
Yes; °C/°F/K
Yes; 16 bit incl. sign
1 MΩ
Yes; 16 bit incl. sign
1 MΩ
Yes; 16 bit incl. sign
1 MΩ
Yes; 16 bit incl. sign
1 MΩ
Technical specifications
45