Technical specifications
Article number
Thermocouple (TC)
Temperature compensation
–
parameterizable
–
Reference channel of the module
–
internal comparison point
–
Reference channel of the group
–
Number of reference channel groups
–
fixed reference temperature
Cable length
shielded, max.
•
Analog value generation for the inputs
Measurement principle
Integration and conversion time/resolution per
channel
Resolution with overrange (bit including
•
sign), max.
Integration time, parameterizable
•
Basic conversion time, including integration
•
time (ms)
–
additional processing time for wire-
break check
Interference voltage suppression for inter-
•
ference frequency f1 in Hz
Conversion time (per channel)
•
Smoothing of measured values
Number of smoothing levels
•
parameterizable
•
Encoder
Connection of signal encoders
for voltage measurement
•
for resistance measurement with two-wire
•
connection
for resistance measurement with three-wire
•
connection
for resistance measurement with four-wire
•
connection
48
6ES7134-6JF00-0CA1
Yes
Yes
Yes; with BaseUnit type A1
Yes
4; Group 0 to 3
Yes
200 m; 50 m with thermocouples
integrating (Sigma-Delta)
16 bit
Yes
2 ms; In the ranges resistance thermometers,
resistors and thermocouples
16.6 / 50 / 60 Hz
180 / 60 / 50 ms
4; None; 4/8/16 times
Yes
Yes
Yes
No
No
Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1)