Input Calibration Procedure; Table 6-7 Set Up Wiring Procedure For 0 To 10 Volts; Figure 6-5 Wiring Connections For Radiamatic, Milliampere, Millivolts, Or Volts (Except 0 To 10 Volts); Figure 6-6 Wiring Connections For 0 To 10 Volts - Honeywell UDC2300 Product Manual

Universal digital indicator
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Figure 6-5 Wiring Connections for Radiamatic, Milliampere, Millivolts, or
0 to 10 Volts
Refer to Figure 6-6 and wire the indicator according to the procedure given in Table 6-7.
Make sure the jumper at S101 is in parked position (Figure 2-2).
Step
Connect the copper leads from the calibrator to the Input terminals as shown in
1
Figure 6-6.
2
Place current source at zero before switching on.
3
Do not switch current sources ON/OFF while connected to the UDC2300 input.

6.5 Input Calibration Procedure

Preliminary Steps
• Apply power and allow the indicator to warm up for 30 minutes before you calibrate.
• Please read Subsection 6.4 "Input Set Up Wiring" before beginning the procedure.
• Make sure you have LOCK set to NONE. See Section 4.4
See Table 6-1 for Voltage vs. Resistance equivalents or 0 % and 100 % range values.
For linear inputs, avoid step changes in inputs. Vary smoothly from initial value to final 100 % value.
10/00
Milliampere,
+
Millivolt, Volt
_
Source
Volts (Except 0 to 10 Volts)

Table 6-7 Set Up Wiring Procedure for 0 to 10 Volts

Volt
Source

Figure 6-6 Wiring Connections for 0 to 10 Volts

UDC2300 Indicator Product Manual
Action
+
1
2
_
3
Input Calibration
8
+
_
7
24876
8
+
_
7
6
R
24877
45