Alarm Setpoints; Table 5-4 Procedure For Displaying Alarm Setpoints - Honeywell UDC2300 Product Manual

Universal digital indicator
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

5.6

Alarm Setpoints

Introduction
An alarm consists of a relay contact and an operator interface indication. The alarm relay
is de-energized if setpoint 1 or setpoint 2 is exceeded.
The alarm relay is energized when the monitored value goes into the allowed region by
more than the hysteresis.
The relay contacts can be wired for normally open (NO) energized or normally closed
(NC) de-energized using internal jumper placement. See Table 2-3 in the Section 2 –
Installation for alarm relay contact information.
There are four alarm setpoints, two for each alarm. The type and state (High or Low) is
selected during configuration. See Subsection 4.6 – Configuration for details.
Alarm Setpoints Display

Table 5-4 Procedure for Displaying Alarm Setpoints

Step
Operation
1
Select Alarm
Set-up Group
Access the Alarm
2
Setpoint Values
Change a value
3
Return to Normal
4
Display
10/00
Press
Until you see:
SET UP
Upper Display = SET
Lower Display = ALARMS
FUNCTION To successively display the alarm setpoints and their values.
Their order of appearance is shown below.
Upper Display = (the alarm setpoint value)
Range values are within the range of the selected
parameters except:
PV RATE OF CHANGE (PVRT) = The amount of PV
change in one minute in engineering units.
Lower Display = A1S1VA = Alarm 1, Setpoint 1
[ ] [ ]
To change any alarm setpoint value in the upper display.
DISPLAY
UDC2300 Indicator Product Manual
Setpoint Rate/Ramp/Program Operation
Result
A1S2VA = Alarm 1, Setpoint 2
A2S1VA = Alarm 2, Setpoint 1
A2S2VA = Alarm 2, Setpoint 2
37

Advertisement

Table of Contents
loading

Table of Contents