Table 6-8 Input Calibration Procedure - Honeywell UDC2300 Product Manual

Universal digital indicator
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Input Calibration
Procedure
The calibration procedure for the Input is listed in Table 6-8.
Step
Operation
Enter Calibration
1
Mode
2
Calibrate 0 %
3
Calibrate 100 %
46

Table 6-8 Input Calibration Procedure

Press
SET UP
Upper Display = CAL (
Lower Display = INPUT1 (10000)
until you see
You will see:
FUNCTION
Upper Display = DIS ( 0 )
Lower Display = CALIN1 (10001)
The calibration sequence is enabled and you will see:
Upper Display = BEGN ( 1 )
Lower Display = CALIN1 (10001)
At the completion of the sequence, the selection
automatically reverts to disable.
You will see:
FUNCTION
Upper Display = APLY ( 2 )
Lower Display = IN1ZRO (10002)
Adjust your calibration device to an output signal equal to
the 0 % range value for your particular input sensor. See
Table 6-1 for Voltage, Degrees, or Resistance
equivalents for 0 % range values.
Wait 15 seconds, then go to the next step.
You will see:
FUNCTION
Upper Display = APLY ( 2 )
Lower Display = IN1SPN (10003)
Adjust your calibration device to an output signal equal to
the 100 % range value for your particular input sensor.
See Table 6-1 for Voltage, Degrees, or Resistance
equivalents for 100 % range values.
Wait 15 seconds, and
If ...
you are calibrating a Thermocouple input go to step 4
you are calibrating other than a
Thermocouple input
UDC2300 Indicator Product Manual
Result
- - - -
)
Then ...
go to step 5
10/00