Preliminary Information; Figure 6-1 Input Wiring Terminals - Honeywell UDC2300 Product Manual

Universal digital indicator
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Sensor Type
W5W26
W5W26 (low)
Honeywell
Radiamatic
Type RH
Type RI
RTD
(IEC Alpha=0.00385)
100 ohms
100 ohms (low)
200 ohms
500 ohms
Linear
Milliamps
(impedance – 249 Ω)
Millivolts
Volts

6.3 Preliminary Information

Disconnect the Field Wiring
Tag and disconnect any field wiring connected to the input terminals on the rear of the
indicator.
Check the Jumper for Input
Before you calibrate the Input, check the internal jumper for the Input to make sure it is
set for the correct input type. The jumper is located at position S101 on the printed wiring
board. Figure 2-2 shows the location of the jumper and position selections.
10/00
PV Input Range
°F
0 to 4200
–18 to2315
0 to 2240
–18 to1227
0 to 3400
–18 to1871
0 to 3200
–18 to1760
-300 to 1200
–184 to649
-300 to 300
–184 to149
-300 to 900
–184 to482
-300 to 900
–184 to482
4 to 20 mA
0 to 20 mA
0 to 10 mV
0 to 50 mV
0 to 100 mV
1 to 5 Volts
0 to 2 Volts
0 to 5 Volts
0 to 10 Volts
Input
Connections

Figure 6-1 Input Wiring Terminals

UDC2300 Indicator Product Manual
°C
0 %
–0.234 mV
–0.234 mV
0.00 mV
0.00 mV
25.18 ohms
25.18 ohms
50.36 ohms
125.90 ohms
4.00 mA
0.00 mA
0.00 mV
0.00 mV
0.00 mV
1.00 Volts
0.00 Volts
0.00 Volts
0.00 Volts
+
8
_
7
R
6
24869I
Input Calibration
Range Values
100 %
37.075 mV
22.283 mV
57.12 mV
60.08 mV
274.96 ohms
156.90 ohms
549.92 ohms
1374.80 ohms
20.00 mA
20.00 mA
10.00 mV
50.00 mV
100.00 mV
5.00 Volts
2.00 Volts
5.00 Volts
10.00 Volts
41