Mitsubishi Electric EMU4-D65 Instruction Manual page 6

Display unit
Hide thumbs Also See for EMU4-D65:

Advertisement

Screen
7(2) Setup the demand time
7 ( 2 ) -1
(1) In 7(2)-1, push the ▲ or
[Measure]
the "6 Demand".
4 DISP.Mode
(2) Push the
5 MEA.Mode
6
Demand
(3) 7(2)-2 will be displayed.
7 ( 2 ) -2
(1) Push the + or - key, and change the Io/Ior demand time value.
[Demand]
(2) Push the
Io/Ior:
5min
(3) 7(2)-1 will be displayed.
8 Setup the electric energy equivalent rate
8-1.
(1) In 8-1, push the
[Measure]
"7 CONV.Wh"
5 MEA.Mode
(2) Push the
6 Demand
7
CONV.Wh
(3) 8-2 will be displayed.
8-2.
(1) Push the ▲
[CONV.Rate]
unit.
1.000
(2) Push the
[Unit]
(3) Transition to the following screen by the setting wiring type.
Non
[1]
2 circuit measurement → To 8-3
non-2 circuit measurement → To 8-1
8-3.
(1) In a similar way as 8-2, change the "CONV.Rate" value and unit of the
[CONV.Rate]
second circuit.
1.000
(2) Push the
[Unit]
(3) 8-1 will be displayed.
Non
[2]
9 Setup the current cut-off rate ( All models except for EMU4-LG1-MB, EMU4-PX4 and EMU4-AX4 )
9-1.
(1) In 9-1,push the ▲ or
[Measure]
"8 A Cut-off".
6 Demand
(2) Push the
7 CONV.Wh
8
A Cut-off
(3) 9-2 will be displayed.
9-2.
(1) Push the
[A Cut-off]
(2) Push the
00.5%
(3) Transition to the following screen by the setting wiring type.
[1]
2 circuit measurement → To 9-3
non-2 circuit measurement → To 9-1
9-3.
(1) In a similar way as 9-2, change the "A Cut-off" value of the second circuit.
[A Cut-off]
(2) Push the
00.5%
(3) 9-1 will be displayed.
[2]
10 Setup the Simple measurement
10-1.
(1) In 10-1, push the ▲ or ▼ key, and move the cursor to the
[Measure]
"9 SimpleMEA".
7 CONV.Wh
(2) Push the
8 A Cut-off
9
SimpleMEA
(3) 10-2 will be displayed.
10-2.
(1) Push the
[SimpleMEA]
(2) Push the
Off
(3) Transition to the following screen by the setting SimpleMEA( [ On ] / [ Off ] )
[ On ] setting → To 10-3
[ Off ] setting → To 10-1
10-3.
(1) Push the ▲ ▼ + - key, and change the power factor value
[FP Set]
In the SimpleMEA.
1.000
(2) Push the
[1]
(3) Transition to the following screen by the setting wiring type.
2 circuit measurement → To 10-4
non-2 circuit measurement → To 10-1
10-4.
(1) In a similar way as 10-3, change the power factor value of the second circuit.
[FP Set]
(2) Push the
1.000
(3) 10-1 will be displayed.
[2]
11
Setup the Ior difference conversion
11-1.
(1) In 11-1, push the ▲ or ▼ key , and move the cursor to the
[Measure]
"10 DIF.CONV".
8 A Cut-off
(2) Push the
9 SimpleMEA
10
DIF.CONV
(3) 11-2 will be displayed.
11-2.
(1) Push the + or - key, and select the Ior difference converted value
[ DIF.CONV ]
( [ On ] / [ Off ] )
(2) Push the
Off
(3) Transition to the following screen by the setting DIF.CONV( [ On ] / [ Off ] ).
[ On ] setting → To 11-3
[ Off ] setting → To 11-1
Operation
EMU4-LG1-MB
▼ key, and move the cursor to
/ Phase key and
/ Phase key, and confirm the setting value.
All models except for EMU4-LG1-MB
▲ or ▼ key, and move the cursor to the
/ Phase key.
- key, and change the "CONV.Rate" value and
/ Phase key , and confirm the setting value.
/ Phase key, and confirm the setting value.
▼ key , and move the cursor to the
/ Phase key.
+ or - key, and change the set value.
/ Phase key , and confirm the setting value.
/ Phase key, and confirm the setting value.
All models except for EMU4-LG1-MB, EMU4-PX4 and EMU4-AX4
/ Phase key.
or - key, and select SimpleMEA ([ On ] / [ Off ]) .
/ Phase key, and confirm the setting value.
/ Phase key,and confirm the setting value.
/ Phase key, and confirm the setting value.
EMU4-LG1-MB only
/ Phase key.
/ Phase key, and confirm the setting value.
- 6 -
Note
[Demand]:0sec⇔5min⇔6min⇔7min⇔8min⇔9min⇔
10min⇔11min⇔12min⇔13min⇔14min⇔
15min⇔20min⇔25min⇔30min⇔
[CONV.Rate]:0.001~10000(1.000)
[Unit]:Non⇔Wh⇔kWh⇔MWh⇔J⇔m
kL⇔sec⇔min⇔hour⇔piece⇔set⇔g⇔kg⇔
t⇔¥⇔$⇔
[ A Cut-off ] :0.1~50.0%(0.5)
A cut-off rate...represent as the ratio of cut-off current
to rated current.
※Measured value is 0A if it is less than the
cut-off current.
[SimpleMEA]:Off⇔On⇔
SimpleMEA...The value set in the electric power and
the power factor as the fixed value.
By measuring the current only, and
calculating the values of the measurement
elements.
[FP Set]:-0.001~1.000~0.000
[DIF.CONV]:Off⇔On⇔
DIF.CONV...To calculate the amount of change from
the Ior difference converted value.
2
3
⇔m
⇔L⇔