Screen
3 Setup the operation time measurement
3-1.
(1) In 3-1, Push the ▲ or
[I/O]
"2 OP.Time".
1 Input
(2) Push the
2
OP.Time
3 Output
(3) 3-2 will be displayed.
3-2.
(1) Push the +
[OP.Time]
(On/Off)
(2) Push the
Off
(3) Transition to the following screen by the model, and setting wiring type and
[1]
existence of the operation time measurement.
Model:EMU4-PX4 → To 3-4
Model:EMU4-PX4 or
2 circuits measuring
Model:Other than EMU4-PX4
only
2 circuit measurement and [ Off ] setting → To 3-4
non-2 circuit measurement and [ Off ] setting → To 3-1
[ On ] setting → To 3-3
3-3.
(1) Push the + or - key, and select the operation time measurement
[OP.Time
mode.
Mode]
(2) Push the
A
[1]
(3) Transition to the following screen by the setting wiring type.
2 circuit measurement → To 3-4
2 circuits measuring
non-2 circuit measurement → To 3-1
only
3-4.
(1) Push the + or - key, and select the operation time measurement.
[OP.Time]
(2) Push the
(3) Transition to the following screen by the model, and setting existence of the
Off
[2]
operation time measurement.
Model:EMU4-PX4 → To 3-6
Model:Other than EMU4-PX4
[ Off ] setting → To 3-1
[ On ] setting → To 3-5
3-5.
(1) Push the + or - key, and select the operation time measurement
[OP.Time
mode.
Mode]
(2) Push the
A
(3) 3-1 will be displayed.
[2]
3-6.
(1) Push the + or - key, and select the operation time measurement.
[OP.Time]
(2) Push the
(3) 3-7 will be displayed.
Off
[3]
3-7.
(1) Push the + or - key, and select the operation time measurement.
[OP.Time]
(2) Push the
(3) 3-1 will be displayed.
Off
[4]
4 Setup Output
EMU4-HM1-MB, EMU4-A2, EMU4-VA2, EMU4-PX4, EMU4-AX4
(
4-1.
(1) In 4-1, Push the ▲ or ▼ key, and move the cursor to the "3 Output".
[I/O]
(2) Push the
1 Input
(3) 4-2 will be displayed.
2 OP.Time
3
Output
4-2.
(1) Push the + or - key, and select the output signal type.
[Output]
(2) Push the
Non
(3) Transition to the following screen by the model, and setting wiring type and
the output signal type.
Model:EMU4-PX4 or EMU4-AX4 → To 4-1
Model:EMU4-HM1-MB, EMU4-A2 or EMU4-VA2
[Non] setting → To 4-1
2 circuit measurement and [Pulse] setting → To 4-3
non-2 circuit measurement and [Pulse] setting → To 4-4
2 circuit measurement and [Alarm] setting → To 4-3
non-2 circuit measurement and [Alarm] setting → To 4-1
4-3
(1) Push the +
[Output]
(2) Push the
(3) Transition to the following screen by setting output signal type.
[ 1 ]
[Pulse] setting → To 4-4
[Alarm] setting → To 4-1
4-4.
(1) Push the ▲
[Pulse]
(2) Push the
(3) 4-1 will be displayed.
0.01
kWh/Pulse
Operation
All models except for EMU4-LG1-MB
(
▼ key, and move the cursor to the
/ Phase key.
or -
key, and select the operation time measurement.
/ Phase key.
/ Phase key.
/ Phase key.
/ Phase key.
/ Phase key.
/ Phase key.
/ Phase key.
/ Phase key.
or -
key, and select the output target.
/ Phase key.
▼
- key, and change the pulse output unit.
+
/ Phase key. Confirm the setting value.
)
[OP.Time]:Off⇔On⇔
EMU4-HM1-MB
[OP.Time Mode]:A⇔x⇔
EMU4-BM1-MB, EMU4-A2, EMU4-VA2
[OP.Time Mode]:A
EMU4-PX4
Input setting value is set contact, this CH is not
displayed.
Operating time is integrated time while the current
measured value is higher than the rated current,
Current cut-off rate when select A.
Operating time is integration time while Contact input
is ON when Contact input.
)
EMU4-HM1-MB, EMU4-A2, EMU4-VA2
[Output]:Non⇔Pulse⇔Alarm⇔
EMU4-PX4, EMU4-AX4
[Output]:Non⇔Alarm⇔Contact⇔
The pulse output unit changes by the full load power.
[Pulse]:
[Output]:1⇔2⇔
* It is set which circuit it does external output, because
- 10 -
Note
Full load power (kW)
Setting range
Wfull<12kW
0.001⇔0.01⇔0.1⇔1⇔
12kW ≤ Wfull < 120kW
0.01⇔0.1⇔1⇔10⇔
120kW ≤ Wfull < 1200kW
0.1⇔1⇔10⇔100⇔
1200kW ≤ Wfull < 12000kW
1⇔10⇔100⇔1000⇔
12000kW ≤ Wfull < 120000kW
10⇔100⇔1000⇔10000⇔
120000kW ≤ Wfull
100⇔1000⇔10000⇔100000⇔
it inputs 2 circuits per a terminal block for 1P2W.
If the target of external output is 1K, 1L connection
side circuit, Set "1".
If the target of external output is 3K, 3L connection
side circuit, Set "2".