Fan Operation; Controls; Customer Hand Over - BONAIRE B18 Installation Operation & Maintenance

B series commercial evaporative air conditioning
Table of Contents

Advertisement

I
, O
& M
NSTALLATION
PERATION
Commissioning
F
O
AN
PERATION
Check that pulleys are correctly aligned.
Check the belt tension is correct. Nominally 15
– 20mm depression.
Check bearings are tight on shaft
Set the fan running and check.
Check that the air is being evenly distributed
through the ductwork.
Make adjustments, as required, to any manual
air dampers that may be fitted.
Fan Motor Current. Check the motor
operating current is not greater the rating plate
value.
o For systems with high statics and
non standard drive check motor
current. Where required, review
pulley requirements relative to the
system static. Where variable pitch
pulleys are fitted adjust accordingly.
o For systems with minimal static eg
straight dropper and plenums,
check motor current. A smaller
motor pulley to standard may be
required.
C
ONTROLS
Check all control functions are working
C
O
USTOMER HAND
VER
Instruct the customer in the use of the product.

Controls

Bleed off
Venting the air via the side of the premises the wind is not blowing from.
Maintenance Requirements
Hand over of the customer's operational manual.
AINTENANCE
Page 17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: