A permanent water supply is required to be connected to the unit. Units have been type
test certified to MP52, Spec101. Certificate No.8663.

Connecting the Water Supply

The water supply pipe work and connection
to the air conditioner must be installed by a
licensed plumber and conform to AS 3500,
state & local plumbing regulations.
Ensure water pressure to the appliance does
not exceed the maximum static pressure of
500kPa (50 m head) as per As 3500 (section
3.3)
The ball valve connection is inside the unit.
Ensure the copper inlet pipe is secured to
prevent movement of the float valve.
The supply pipe should be 12mm copper pipe or similar approved. A ¼ turn ball
isolating valve must be installed on the supply pipe near the unit for ease of
maintenance. Do not use duo or non-return valves of any kind including stop taps
with jumper washer.
NOTE: Non return type valves can have and effect on the operation of the
water solenoid valves. Lock up and damage can be caused.
Fit water supply tap close to the unit to assist in routine servicing.
Before connecting the supply pipe flush it of any swarf or debris that may cause the
float valve to leak.
NOTE: In areas where water pipes freeze, provisions will be needed to drain
the water piping to prevent damage to the air conditioner.