6 Installation
7. Connect the DC main cables to the busbars for the DC main cables (torque: 60 Nm) (see
Section 6.1, page 25). To do this, use only the fastening material already attached to the
busbars and do not connect more than two DC main cables to each busbar.
8. Ensure that the DC main cables are securely attached.
9. Secure the DC main cables to the external cable support rail.
6.3.4
Connecting the DC Main Cables to the Busbar using V Box
Terminals

6.3.4.1 Requirements and Conditions

Cable requirements for connection with V box terminals:
☐ Use copper or aluminum cables only.
☐ The cables must be designed for the maximum PV voltage.
☐ The cables must have double or reinforced insulation.
☐ Maximum number of cables per potential: 2
☐ Permitted cable cross-section: 70 mm
☐ Permitted conductor cross-section:
Cable type
Round, single-strand
Round, multi-strand
Sectoral, single-strand
Sectoral, multi-strand
Additionally required mounting material (not included in the scope of delivery):
☐ Clean cloth
☐ Ethanol cleaning agent
32
SSMUXX1015-BE-en-14
2
2
to 300 mm
Conductor cross-section per potential
2
70 mm
 to 150 mm
2
70 mm
 to 300 mm
2
70 mm
 to 240 mm
2
70 mm
 to 240 mm
SMA Solar Technology AG
2
2
2
2
Operating Manual