13 Integration Points List - Water-to-Air Standard Software 7.05.03

Integration Points
BACnet
MODBUS
Point Description
#
Name
Type
Object
Name
Type
ID
1
BAS CO₂ Sensor Value
bas_CO₂_val_1
AV:49
fl oat value
2
BAS Mixed Air Temp
bas_mat_1
AV:86
fl oat value
BAS Outside Air
3
effective_oat_1
AV:29
fl oat value
Temperature
4
BAS RH Sensor Value
bas_rh_sen_val_1
AV:56
fl oat value
BAS Temperature
5
bas_sen_val_1
AV:19
fl oat value
Sensor Value
Evaporator Coil
6
coil_cfg_1
AV:94
fl oat value
Confi guration Selection
Compressor Control
7
comp_mode_1
AV:64
fl oat value
Mode
8
Compressor Stages
cmp_stgs_1
AV:14
fl oat value
Compressor Stages
9
stages_1
AV:114
fl oat value
Selection
10
Control Source
ctrl_source_1
AV:15
fl oat value
Cooling Demand
11
clg_pct_1
AV:13
fl oat value
Percentage
12
IN-2 Mode Status
ui2_mode_status_1
AV:18
fl oat value
Table 23
Data subject to change
N2
LON
Read
Only
SNVT
Register
Type
ID
Name
SNVT
#
40001
data fl oat
1
1
nviBasCO₂Val
SNVT_ppm(29)
40003
data fl oat
2
SNVT_
40005
data fl oat
3
0
nviEffectiveOAT
temp_p(105)
SNVT_lev_
40007
data fl oat
4
15
nviBasRhSenVal
percent(81)
SNVT_
40009
data fl oat
5
2
nviBasSenVal
temp_p(105)
40011
data fl oat
6
40013
data fl oat
8
SNVT_count_
40001
data fl oat
7
16
nvoCmpStgs
inc(9)
40107
data fl oat
79
SNVT_count_
40023
data fl oat
12
3
nviCtrlSource
inc(9)
40025
data fl oat
13
40033
data fl oat
55
Integration Points
Point Description
#
Name
Description
BAS CO₂ Sensor Value in PPM
Default: 1001 PPM
BAS Mixed Air Temperature Value
Current Alarm
in °F
13
Condition Status
Default: 66.5 °F
Effective Outside Air Temperature
in °F
Default: 60 °F
RH Sensor Value Supplied by BAS
in %
Default: 56 %RH
BAS Zone Temperature Sensor
Value in °F
Damper Occupancy
Default: 74 °F
14
Selection
Coil Confi guration Setup
0 = Parallel (Default)
1 = Series
Compressor Mode Setup
0 = Zone Control - ZS (Default)
1 = Discharge Air Control
2 = Zone Control - BAS Sensor
3 = Zone Control - Remote Sensor
Reports Confi guration Status of
DI5 Mode (Digital
Compressor Stages
15
Input 5)
1 = 1 Compressor 1 Stage
2 = 2 Compressor 2 Stages
5 = 1 Compressor 2 Stages
Selected Compressor Stages
(Confi gured at Factory)
1 = 1 Compressor 1 Stage
2 = 2 Compressor 2 Stages
5 = 1 Compressor 2 Stages
(Default)
Discharged Air
16
Temperature Setpoint
Control Source for Occupancy
Setup
Effective Cooling
17
0 = Digital Input Enable (e.g. Room
Setpoint
Occupancy Sensor)
1 = Keypad Schedule
18
Effect Disch Air Temp
2 = BAS Occupancy Command
(Default)
3 = Factory Use Only
Entering Water
19
4 = Manual On-Continuous
Temperature
Cooling Status in Demand Percent,
Effective Heating
20
%
Setpoint
Modulating Damper
Reports how the controller Input
21
eff_dpr_pos_screen_1
Position
#2 (IN-2) is confi gured
0 = Not Used
1 = Zone Remote Sensor
22
Zone Humidity
eff_zone_humid_1
2 = Outdoor Air Temperature
Sensor
Leaving Water
3 = Entering Water Temperature
23
Temperature (LWT)
Sensor
4 = Mixed Air Temperature Sensor
Mixed Air Temperature
5 = Relative Humidity Sensor
24
(MAT)
(Probe)
6 = Digital Enable (e.g. Room
Outdoor Air
Occupancy Sensor)
25
Temperature (OAT)
7 = Return Air Temperature Sensor
Table 24
Page____ of ____
BACnet
MODBUS
N2
Type
SNVT
Object
Name
Register
Type
ID
ID
Type
#
current_alarm_1
AV:17
fl oat value
40003
data fl oat
9
17
mdpr_occ_sel_1
AV:97
fl oat value
40031
data fl oat
16
di5_mode_1
AV:60
fl oat value
40015
data fl oat
10
dat_stpt_1
AV:30
fl oat value
40017
data fl oat
11
18
eff_clg_stpt_1
AV:5
fl oat value
40039
data fl oat
20
4
eff_dat_1
AV:10
fl oat value
40011
data fl oat
18
21
eff_ewt_1
AV:62
fl oat value
40013
data fl oat
19
22
eff_htg_stpt_1
AV:6
fl oat value
40045
data fl oat
23
5
AV:81
fl oat value
40047
data fl oat
24
AV:20
fl oat value
40021
data fl oat
26
24
eff_lwt_1
AV:11
fl oat value
40015
data fl oat
21
23
eff_mat_1
AV:87
fl oat value
40017
data fl oat
22
eff_oat_1
AV:75
fl oat value
40055
data fl oat
28
6
Applications Manual
LON
Read
Description
Only
Name
SNVT
Alarm Status of unit:
0 = No Alarm,
1-10 = UPM Fault Code
20 = Output Overridden via Keypad
30 = Sensor Failure
40 = Leaving Water Temp Alarm
50 = Zone Temp Alarm
SNVT_count_
nvoCurrentAlarm
60 = Discharge Air Temperature
inc(9)
Alarm
70 = Filter Alarm/Compressors 1 &
2 Runtime
80 = Zone Humidity Alarm
90 = High CO₂ Level Alarm
100 = Differential Pressure Switch
(DPS) Alarm"
Damper Occupancy Selection
Setup
0 = Disabled
1 = Occupied (Default)
2 = Unoccupied
3 = Any Occupancy
Controller Input #5 Confi guration
Selection
0 = Dirty Filter Switch
1 = Entering Water Temp Sensor -
Economizer/Boilerless
2 = Differential Pressure Switch
3 = Secondary Condensate Pan
4 = Fan Status Switch
5 = Valve End Switch
6 = Damper End Switch
7 = Smoke Detector Switch
8 = Pump Status Switch
9 = MIxed Air Temp Sensor - Mixed
Air Control
10 = Input Expansion Module (IEM)
11 = Not Used (Default)
Discharged Air Temperature
SNVT_
nviDatStpt
Setpoint Setup in °F
temp_p(105)
Default: 65 °F
SNVT_
Effective Cooling Setpoint (after
nvoEffClgStpt
temp_p(105)
setpoint adjustment applied) in °F
SNVT_
Discharge Air Temperature (DAT)
nvoEffDat
temp_p(105)
in °F
SNVT_
Water Side Economizer Effective
nvoEffEwt
temp_p(105)
Entering Water Temperature in °F
SNVT_
Effective Heating Setpoint (after
nvoEffHtgStpt
temp_p(105)
setpoint adjustment applied) in °F
Effective Outside Air Damper
Position in %
SNVT_lev_
Effective Zone Humidity in Percent
nvoEffZoneHumid
percent(81)
RH (%)
SNVT_
Effective Leaving Water
nvoEffLwt
temp_p(105)
Temperature Status in °F
Effective Mixed Air Temperature
in °F
SNVT_
Effective Outdoor Temperature
nvoEffOat
temp_p(105)
Status in °F
Bosch Thermotechnology Corp.