Bosch FHP560 Applications Manual page 29

Multi-protocol heat pump controller. for integration with systems running industry standard protocols
Hide thumbs Also See for FHP560:
Table of Contents

Advertisement

Applications Manual
Integration Points
BACnet
MODBUS
Point Description
#
Name
Type
Object
Name
Register
ID
Type
26
Zone Temperature
eff_zone_temp_1
AV:7
fl oat value
Hot Gas Reheat
27
eff_hgr_mod_vlv1_1
AV:28
fl oat value
Modulating Valve Status
28
Static Air Fan Speed
eff_sa_fan_speed_1
AV:55
fl oat value
Supply Air Duct Static
29
eff_sa_sta_press_1
AV:53
fl oat value
Pressure
30
Zone CO₂ Level
eff_zn_CO₂_lev_1
AV:25
fl oat value
Compressor Enabled
31
enabled_clstages_1
AV:68
fl oat value
Stages
Input Expansion Module
32
iem_mode_1
AV:50
fl oat value
Mode
BAS Relative Humidity
33
rh_bas_sel_1
AV:51
fl oat value
Enable/Disable
Heating Demand
34
htg_pct_1
AV:12
fl oat value
Percentage
Mix Air Temperature
35
mat_sel_status_1
AV:84
fl oat value
Source Status
Mixed Air Temperature
36
mat_sel_1
AV:85
fl oat value
Sensor
Minimum Damper
37
min_mdpr_pos_1
AV:79
fl oat value
Position
Analog Output 2
38
ao2_cfg_sel_1
AV:83
fl oat value
Options Confi guration
Table 25
Bosch Thermotechnology Corp.
N2
LON
Read
Only
SNVT
Type
ID
Name
SNVT
#
40057
data fl oat
29
SNVT_lev_
40005
data fl oat
14
19
nvoEffHgrModVlv1
percent(81)
SNVT_lev_
40007
data fl oat
15
20
nvoEffSaFanSpeed
percent(81)
40009
data fl oat
17
40065
data fl oat
33
40023
data fl oat
27
40085
data fl oat
63
SNVT_count_
40109
data fl oat
80
57
nviRhBasSel
inc(9)
40073
data fl oat
37
40025
data fl oat
30
40019
data fl oat
31
40079
data fl oat
40
SNVT_count_
40089
data fl oat
65
52
nviAo2CfgSel
inc(9)
Integration Points
Point Description
Description
#
Name
Effective Zone Temperature Status
in °F
Effective Hot Gas Reheat
Analog Output 1
39
Modulating Valve Output Status
Options Confi guration
Effective Static Air Fan Speed in %
Effective Static Air Pressure Sensor
Status in H2O"
Mixed Air Temperature
40
Setpoint
Effective Zone CO₂ Levels in PPM
Compressor Stages Enabled
41
Unit Mode Status
IEM Confi guration Setup
0 = Dirty Filter Switch, Fan Status
Switch, Valve End Switch
(Default)
1 = Smoke Detector Switch, Fan
Status Switch, Valve End
Switch
Single Reset/
2 = Dirty Filter Switch, Fan Status
42
Free Cooling Reset
Switch, Differential Pressure
Temperature
Switch
3 = Smoke Detector Switch, Fan
Status Switch, Dirty Filter
Switch
Part Cool Reset
4 = Dirty Filter Switch, Fan Status
43
Temperature
Switch, Damper End Switch
5 = Smoke Detector Switch, Fan
Status Switch, Secondary
Drain Pan
6 = Dirty Filter Switch, Fan Status
Full Cool Reset
44
Switch, Pump Status Switch
Temperature
7 = None
RH Sensor Source Selection
0 = BAS RH Sensor
Heating Reset
45
Temperature
1 = Hard-Wired RH Sensor
(Default)
Heating Capacity in %
Temperature Reset
46
Mode
Mixed Air Temperature Sensor
Source Status
0 = BAS MAT
1 = Wired MAT"
Outside Air
47
Temperature Sensor
Mixed Air Temperature Sensor
Source Setup
0 = BAS MAT Sensor
1 = Hard-Wired MAT Sensor
Outside Air
(Default)
48
Temperature Sensor
Source Status
Minimum Damper Position Setup
Default = 10% Open
49
Setpoint
Options Confi guration - Controller
Analog Output #2 (AO-2)
0 = Not Used (Default)
1 = Modulating Hot Gas Reheat
50
Setpoint
Valve Control
Table 26
Page____ of ____
BACnet
MODBUS
N2
Type
Object
SNVT
Name
Register
Type
ID
ID
Type
#
ao1_cfg_sel_1
AV:82
fl oat value
40087
data fl oat
64
51
mat_stpt_1
AV:90
fl oat value
40021
data fl oat
32
mode_status_1
AV:24
fl oat value
40027
data fl oat
34
25
oat_reset1_1
AV:69
fl oat value
40027
data fl oat
35
oat_reset2_1
AV:72
fl oat value
40029
data fl oat
36
oat_reset3_1
AV:74
fl oat value
40033
data fl oat
38
oat_reset_ht_1
AV:92
fl oat value
40035
data fl oat
39
oat_rst_mode_1
AV:71
fl oat value
40037
data fl oat
41
oat_sel_1
AV:73
fl oat value
40041
data fl oat
42
oat_sel_sta_1
AV:78
fl oat value
40029
data fl oat
43
occ_clg_stpt_1
AV:4
fl oat value
40103
data fl oat
52
9
occ_htg_stpt_1
AV:2
fl oat value
40105
data fl oat
53
10
FHP560 Controller | 29
LON
Read
Description
Only
Name
SNVT
Options Confi guration - Controller
Analog Output #1 (AO-1)
0 = Not Used (Default)
SNVT_count_
1 = Variable Frequence Drive Signal
nviAo1CfgSel
inc(9)
Control
2 = Mixed Air SCR Preheat Control
3 = SCR Controlled Aux Electric
Heat
Mixed Air Temperature Setpoint
Default: 42 °F, Minimum: 40°F,
Maximum: 60°F
Unit Mode of Operation Selection
Status
0 = Cooling only
SNVT_count_
1 = Aux Heat
nvoModeStatus
inc(9)
2 = Heat Pump
3 = Heat Pump + Aux Heat
4 = Heat Pump + Hot Gas Re-Heat
5 = Cooling + Hot Gas Re-Heat"
Outside Air Temperature (Free
Cooling Temperature) Operation in
°F or Single Reset Temperature
Default: 50 °F
Outside Air Temperature (Stage 1
Cooling Temperature) Operation
in °F
Default: 60 °F
Outside Air Temperature (Stage 2
Cooling Temperature) Operation
in °F
Default: 75 °F
Outside Air Temperature Reset
Mixed Air (Stage 1 Heating)
Operation in °F Default: 40 °F
Outside Air Temperature Reset
Setup
0 = Single
1 = Multiple (Default)
Outside Air Temperature Sensor
Source Setup
1 = BAS OAT Sensor
2 = Hard-Wired OAT Sensor
(Default)
Outside Air Temperature Sensor
Source Status
0 = BAS OAT Source
1 = Hard-Wired OAT Source
Occupied Cooling Setpoint Setup
SNVT_
nviOccClgStpt
in °F
temp_p(105)
Default: 74 °F
Occupied Heating Setpoint Setup
SNVT_
nviOccHtgStpt
in °F
temp_p(105)
Default: 70 °F