11.14 HP + HGRH + LP + (DFS-PSS)

TO BACnet
MS/TP
NETWORK
LWTS
DATS
IEM
T1
C
C
T2
B
641-264
B
A
A
STANDARD COMPONENTS:
DATS - DISCHARGE AIR TEMPERATURE SENSOR
LWTS - LEAVING WATER TEMPERATURE SENSOR
Bosch Thermotechnology Corp.
FHP560
UNIT TERMINAL BLOCK
REFER TO UNIT WIRING DIAGRAM FOR FURTHER DETAILS
Heat Pump Sequence of Operation – HP + HGRH + LP + (DFS-PSS)
Supply Fan Start/Stop:
The supply fan will be started according to the schedule. After the supply fan has been started the control sequence will be enabled.
Zone Control:
The compressor will cycle to maintain the zone temperature at setpoint.
Heat Pump Control:
When the zone temperature falls below the zone temperature setpoint the reversing valve will be disabled to provide heating when the
compressor is running. When the zone temperature rises above the zone temperature setpoint the reversing valve will be enabled to provide
cooling when the compressor is running.
Night Setback:
When in "unoccupied", the unit will cycle as necessary to maintain the night setback zone temperature at setpoint.
Shutdown:
When the unit is shutdown by either a stop command or system safety the unit will be set as follows:
Supply fan will be on (user configurable)
Compressor(s) will be off
Dirty Filter Switch:
A fi eld installed status switch is used to provide a contact closure at the confi gured input (IN-5 or IEM) when the fi lter is ready to be serviced.
An alarm is generated immediately after the switch closes, and is available on a ZS Pro sensor, BACview interface, or over a network.
Hot Gas Reheat:
Once the heat/cool setpoint has been satisfi ed and relative humidity is above setpoint, the unit will operate in hot-gas reheat mode to actively
remove humidity from the space until the the humidity setpoint has been satisfi ed, or there's another call for heating or cooling.
Relative humidity readings may be acquired from a space ZS combo Pro or base sensor, 0-5V sensor in IN-1/IN-2, or over a network; software must
be confi gured accordingly.
Circulating Water Pump (Loop Pump):
Factory installed loop pump with with optional current sensor for pump status verifi cation must be confi gured by the equipment integrator.
Upon a call for compressor operation the pump is indexed to run via BO-5 after 20 secs. Compressor operation is not enabled until sensor switch
is closed (pump is energized and running).
Pump status is verifi ed via the Pump Status Switch (current sensor) within 15 secs of pump enable command.
If Pump Status Switch (PSS) does not close within the 15 secs, pss fail alarm is initiated. If pump runs without command from BO-5, pump in hand
alarm is initiated.
Compressor operation is disabled 20 secs after PSS opens (fails) when pump has been indexed to run.
HEAT PUMP
Point Name
AI
Zone Temperature
X
Heating Setpoint
Cooling Setpoint
Supply Fan Command
Compressor Stage 1 Output
Compressor Stage 2 Output
Reversing Valve Command
Occupied Command
Discharge Air Temperature
X
Leaving Water Temperature
X
Loop Pump Command
Pump Status
Dehumidifi cation Setpoint
Reheat Status
Reheat On/Off (Rh S/S)
High Return Air Humidity
Zone Humidity
X
Filter Status
Filter Change Required
Condensate Overfl ow
Lockout Alarm
Schedule
4
Totals
Table 22
Page____ of ____
Hardware Points
Software Points
AO
BI
BO
AV
BV
Sched
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
0
3
5
5
3
1
Total Hardware
Total Software
12
25
FHP560 Controller | 25
Show On
Graphic
Trend
Alarm
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
11
5
16
16
Data subject to change

Advertisement

Table of Contents
loading

Table of Contents