3 2 | FHP560 Controller
Integration Points
BACnet
MODBUS
Point Description
#
Name
Type
Object
Name
Register
ID
Type
Outdoor RH low limit
88
rh_lo_lim_aecon_1
AV:119
fl oat value
for Air Econ
89
Compressor Status
comp_state_1
AV:120
fl oat value
SCR Electric Heat
90
mat_pid_1
AV:121
fl oat value
Output
91
Alarm Status
alm_status_1
BV:24
discrete in
92
Aux Heat Output Cmd
aux_htg_cmd_1
BV:20
discrete in
UPM Safety - Brownout
93
brn_2st_1
BV:10
discrete in
Alarm
Occupancy Command
94
occupancy_cmd_1
BV:1
discrete out
(BAS)
95
Compressor 1 Runtime
comp1_rntm_1
BV:35
discrete in
96
Compressor 2 Runtime
comp2_rntm_1
BV:36
discrete in
Compressor 1 Runtime
97
cmp1_rntm_rst_1
BV:13 discrete out
Reset
Compressor 2 Runtime
98
cmp2_rntm_rst_1
BV:14 discrete out
Reset
Comp Stage1 Output
99
cmp_stg1_cmd_1
BV:11
discrete in
Cmd
Comp Stage2 Output
100
cmp_stg2_cmd_1
BV:12
discrete in
Cmd
Table 31
Data subject to change
N2
LON
Read
Only
SNVT
Type
ID
Name
SNVT
#
40119
data fl oat
89
40053
data fl oat
90
40055
data fl oat
91
SNVT_
10002
binary in
2
30
nvoAlmStatus
switch(95)
SNVT_
10003
binary in
3
31
nvoAuxHtgCmd
switch(95)
SNVT_
10004
binary in
4
32
nvoBrn2st
switch(95)
SNVT_
1
binary out
1
12
nviOccupancyCmd
switch(95)
10006
binary in
6
10007
binary in
7
SNVT_
2
binary out
10
35
nviCmp1RntmRst
switch(95)
SNVT_
3
binary out
11
36
nviCmp2RntmRst
switch(95)
SNVT_
10008
binary in
8
33
nvoCmpStg1Cmd
switch(95)
SNVT_
10009
binary in
9
34
nvoCmpStg2Cmd
switch(95)
Integration Points
Point Description
Description
#
Name
Air Economizer Option: range
UPM Safety - High
101
setting for Outside Air Relative
Condensate Alarm
Humidity (Low Limit) in %
Default: 40 %
Secondary Condensate
Reports compressor state for heat
102
Pump Alarm
pump units:
0 = Normal/Off
1 = Compressor Locked
2 = Compressor Overriden ""ON""
3 = Compressor Shutdown/Alarm
103
Continuous Fan
SCR controlled Electric Heat
Output in %
Network Status indicating alarm
condition in unit (see ""Current
Economizer Cooling
Alarm"" for more information)
104
Command
0 = System Normal
1 = System in Alarm"
Auxiliary Heat Output Status
High Cooling Supply Air
0 = Aux Heat Off
105
Temperature in DAC
1 = Aux Heat On
Brown Out Alarm Status
0 = Normal
Condenser Water Valve
1 = BRN Alarm Enabled
106
Output
BAS Occupancy Command
0 = Unoccupied (Default)
Discharge Air
1 = Occupied (Enables Unit
107
Temperature Sensor
Operation)
Compressor 1 Runtime Alarm
0 = Normal
1 = Timer Has Expired
108
Damper End Switch
(Default: >8760 Hours)
Compressor 2 Runtime Alarm
Status
109
Damper Command
0 = Normal
1 = Timer Has Expired
(Default: >8760 Hours)
High Discharge Air
Compressor 1 Runtime Reset.
110
Temperature
Momentary On/Off required.
0 = Reset Off (Default)
1 = Reset On
Compressor 2 Runtime Reset.
Discharge Air
111
Momentary On/Off required.
Temperature Alarm
0 = Reset Off (Default)
1 = Reset On
Compressor Stage 1 Output Status
Digital Override Lock
112
0 = Compressor 1 Off
Alarm
1 = Compressor 1 On
Differential Pressure
Compressor Stage 2 Output Status
113
Switch (DPS) Alarm
0 = Compressor 2 Off
1 = Compressor 2 On
Table 32
Page____ of ____
BACnet
MODBUS
N2
Type
Object
SNVT
Name
Register
Type
ID
ID
Type
#
con_2st_1
BV:9
discrete in
10010
binary in
12
37
conpump_1
BV:50
discrete in
10012
binary in
14
cont_fan_1
BV:18 discrete out
5
binary out
15
38
clg_econ_1
BV:92
discrete in
10015
binary in
16
csat_hi_1
BV:86
discrete in
10016
binary in
17
cwv_cmd_1
BV:79
discrete in
10017
binary in
18
da_sen_1
BV:31
discrete in
10018
binary in
19
des_status_1
BV:93
discrete in
10019
binary in
20
damper_cmd_1
BV:49
discrete in
10020
binary in
21
39
dat_hi_1
BV:29
discrete in
10021
binary in
22
dat_lo_1
BV:30
discrete in
10022
binary in
23
do_lock_1
BV:37
discrete in
10023
binary in
24
dps_alarm_1
BV:77
discrete in
10024
binary in
25
Applications Manual
LON
Read
Description
Only
Name
SNVT
Condensate Drain Alarm
SNVT_
nvoCon2st
0 = Normal
switch(95)
1 = Alarm Active
Secondary Condensate Pump
Alarm
0 = Normal
1 = Alarm Active
Confi gures Fan Operation for
Continuous or Auto
0 = Cycle Fan with Compressor
SNVT_
nviContFan
Operation (Auto)
switch(95)
1 = Continuous Fan Operation
when Occupied or in NSB
(Default)
Cooling Economizer Status
0 = On
1 = Off
High Cooling Supply Air
Temperature during Discharge Air
Control Alarm
0 = Normal
1 = Alarm Active
Condenser Water Valve Status
0 = Closed
1 = Open
Discharge Air Temperature Sensor
Alarm
0 = Sensor Normal
1 = Sensor Failure Alarm
Damper End Switch Status
0 = Damper Closed
1 = Damper Open
Damper Position Output Status
SNVT_
nvoDamperCmd
0 = Closed
switch(95)
1 = Open
Discharge Air Temperature Sensor
Alarm (High Threshold - Cooling)
0 = Normal
1 = Alarm (Default: >70 °F)
Discharge Air Temperature Sensor
Alarm (Low Threshold - Heating)
0 = Normal
1 = Low DAT Alarm
(Default: <75 °F)
Digital Override Lock Alarm
0 = Normal
1 = Digital Override Enabled Alarm
Differential Pressure Switch Alarm
0 = Normal
1 = Alarm