Hp + Eh + Cwv + (Sds-Fss-Ves) - Bosch FHP560 Applications Manual

Multi-protocol heat pump controller. for integration with systems running industry standard protocols
Hide thumbs Also See for FHP560:
Table of Contents

Advertisement

2 4 | FHP560 Controller

11.13 HP + EH + CWV + (SDS-FSS-VES)

TO BACnet
MS/TP
NETWORK
RTS
LWTS
DATS
IEM
T1
C
T2
C
B
641-264
B
A
A
STANDARD COMPONENTS:
DATS - DISCHARGE AIR TEMPERATURE SENSOR
LWTS - LEAVING WATER TEMPERATURE SENSOR
RTS
- REMOTE TEMPERATURE SENSOR
Data subject to change
FHP560
UNIT TERMINAL BLOCK
REFER TO UNIT WIRING DIAGRAM FOR FURTHER DETAILS
Heat Pump Sequence of Operation – HP + EH + CWV + (SDS-FSS-VES)
Supply Fan Start/Stop:
The supply fan will be started according to the schedule. After the supply fan has been started the control sequence will be enabled.
Zone Control:
The compressor will cycle to maintain the zone temperature at setpoint.
Heat Pump Control:
When the zone temperature falls below the zone temperature setpoint the reversing valve will be disabled to provide heating when the
compressor is running. When the zone temperature rises above the zone temperature setpoint the reversing valve will be enabled to provide
cooling when the compressor is running.
Night Setback:
When in "unoccupied", the unit will cycle as necessary to maintain the night setback zone temperature at setpoint.
Smoke Detector Switch:
A fi eld installed smoke detector provides a contact closure at the confi gured input (IN-5 or IEM) during a smoke event, and will initiate emergency
shutdown procedures after 5 seconds.
When the unit is shutdown by the smoke detector the unit will be set as follows:
Supply fan will be off (user configurable)
Compressor(s) will be off
The unit may be confi gured to operate the fan during a smoke event for specifi c safety applications; system integrator must determine the
appropriate fan behavior.
Fan Status Switch:
The status output from a factory-installed current sensor provides a contact closure at the confi gured input (IN-5 or IEM) to prove fan operation.
The fan command output is disabled if a contact closure is not detected 35 secs after the unit fan is indexed on by the controller.
Auxiliary Electric Heat:
Electric Heat (EH) option may be factory or fi eld installed and must be confi gured by the equipment integrator. Only one (1) stage of auxiliary
electric heat is supported and may be confi gured for BO-4 (single stage compressor units) or BO-5 (dual stage compressor units).
Upon a call for heating with demand greater than 90% (user confi gurable), the EH signal will be enabled to maintain setpoint at the confi gured
output as follows:
Straight cool units: enabled with no delay
Single stage heat pump units: enabled 5 mins after first stage of mechanical heat if demand is still above 90%.
Dual stage heat pump units: enabled 5 mins after second stage of mechanical heat if demand is still above 90%.
Condenser Water Valve:
Factory installed loop valve with valve end switch (VES) option must be confi gured by the equipment integrator. Upon a call for compressor
operation the normally closed valve is indexed to open via BO-5 after 2.5 Mins. Compressor operation is not enabled until Valve End Switch is
engaged (valve fully open). Valve open status is verifi ed via the VES within 1.5 Mins of valve enable command.
If VES contacts do not engage within the specifi ed time, VES fail alarm is initiated. If valve opens without command from BO-5, valve in hand alarm
is initiated. Compressor operation is disabled 20 secs after VES opens (fails) when loop valve has been indexed to open.
HEAT PUMP
Point Name
Zone Temperature
Heating Setpoint
Cooling Setpoint
Supply Fan Command
Compressor Stage 1 Output
Compressor Stage 2 Output
Reversing Valve Command
Occupied Command
Discharge Air Temperature
Leaving Water Temperature
Loop Valve Command
Valve End Switch (Valve Status)
Aux Electric Heat Output
Fan Status
Smoke Detector Status
Condensate Overfl ow
Lockout Alarm
Schedule
Totals
Table 21
Page____ of ____
Hardware Points
Software Points
AI
AO
BI
BO
AV
BV
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
3
0
4
5
3
3
Total Hardware
Total Software
12
Applications Manual
Show On
Sched
Trend
Alarm
Graphic
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
1
8
4
12
19
12
Bosch Thermotechnology Corp.