2. Close "Q1 - UPS Output switch" (Pos. I).
•
The Load is supplied by the Utility through the Automatic Bypass.
•
Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start.
•
At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
The Synoptic Diagram must display the status
"LOAD SUPPLIED BY AUTOMATIC BYPASS".
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-link 1 and DC-link 2 has reached 400Vdc (see screen MEASURES /
Rectifier)!
Attention: check the right DC polarities on both side of the switch/fuse holder!
3. Connect the Battery to the UPS by closing the
"External Battery Protections" and close, if present,
the "CB3 – External Battery switch" (option).
NOTE !
Before performing the next procedure (4) make sure that the LED 3 (Booster/Battery
charger) is lit.
4. Insert the Inverter performing the command "Inverter ON".
Perform the "Inverter ON" command from the screen:
Commands 1 / Inverter / ON.
• Soft-start of Inverter indicated with blinking LED 2 (Inverter).
• At the end of Soft-start the LED 2 (Inverter) remains lit.
•
The Load is automatically transferred from Automatic Bypass to Inverter.
•
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status
"LOAD SUPPLIED BY INVERTER".
5. Operation mode selection.
TLE Series 160 - 500 is delivered normally selected for permanent VFI operation.
If available, the eBoost™ Operation Mode can be enabled and the eBoost Start Time & eBoost Stop Time can
be programmed for each day of the week (see Section 6.4 SETUP / eBoost).
NOTE !
The Battery must be charged for at least 10 hours, in order to ensure the full backup
runtime in case of a Utility Failure.
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Critical Power
END OF PROCEDURE
Page 59/91
User Manual TLE Series 160 - 500 UL S2B