TEST Koy:
I Fire Test
Entry of the security code followed by depression of the TEST
key will mitiate a lest of the sensing circuitry by shorting all
zones. The siren will sound from battery power tor 3 seconds
and "6" will be displayed at the console if all the sensing cir-
cuitry is operating and as a test of all of the lightable seg-
ments of the display. In addition. the system may momentarily
exhibit FIRE TROUBLE and will interrupt smoke detector DC
power for 10 seconds.
b. Test Roporl and Insteiiation Test
15 seconds following the fire test, the system will automati-
cally enter the installation test mode provided the user did not
enter the security code followed by depression of the OFF
key.
When in the installation test mode. the console will beep every
15 seconds to remind the user that the system is not active. A
lest report to the central station is initiated when entering this
mode. Activation of any zone causes a brief % second sound-
ing from the exterior alarm sounder(s), as well as vtsual zone
annunciation on the console's zone identification display. The.
installation test mode will not time-out. It must be ended man-
ually by keying the security code followed by depression of
the OFF key.
2 Audlbie Signals
Rm Alarm: Interrupted. rapidly alternating two-tone sound
OthW
accompanied by lighting of the FIRE LED.
hJdibfe ANfm8: Continuous rapidly alternating two-tone sound
accomoanied bv liohtino of ALARM LED.
System Tumed OFF or'Fallum io Amp-Single brief tone
System Amid
AWAY: Two brief tones
SpNml Amed STAR Three brief tones
NON: Confirmation Of arming tones will not be produced when
the system is directly armed from the AWAY mode into
the.STAY mode and vice versa.
Tlouti
Rapidly pulsing tones tor a trouble or for a loss of AC
power beyond the programmed time period.
w
AC Power Outage: After a prolonged AC power
outage beyond the program-
med time penod the Control/
Commumcator may eventually
go into a shutdown condition.
The console will emit a low tone
and tts Zone I.D. Display will
indicate a "C". The tone can be
silenced by depressing a 4 on
the keypad.
BrNfy Weming: Slowly pulsing tones activated during the entry
delay penod.
Nota: ff the system is armed (e.g. AWAY) and the user opens
the entry/exit door and enters (code) + STAY with the
door still open, the system will correctly not arm in the
STAY mode (it disarms). However, the entry warning
tone will continue until (code) + OFF is keyed.
Chime Annunciation:
Single tone each time a chime annuncia-
tioioeabled
zone is tautted when in this
Memory of Alarm: Rapidly pulsing tones activated during the
entry delay period subsequent to an alarm or
after disarming subsequent to an atarm that
has timed out.
Key Depression Feed-
Brief buzz tone for each key
depressed.
Note: Keying of the fit
digit of the security code will imme-
diately silence any pulsating tones or alarm sounds that
the Console may be emitting (any alarms from external
sounders will continue, however). This will allow the con-
firmation tone emitted by the Console to be heard as
each key on the keypad is depressed. However. this will
also cause the confiition
of arming/disarming tones t0
be suppressed. If the entire security code. plus OFF. are
not keyed within 10 seconds, the pulsating tones or atarm
sounds will resume at the Console.
C. FUNCTIONAL
OESCRIPTiON, No 5314 REMOTE KEYPAD (Ses
Oiagmm 7)
1. Keyyprd and LEOs:
Note: While entries are being
made
via the keypad. if more
than two eeconds elapse between successive key
entrtes, all prror entered informatron will be erased. thus
requrring the entry sequence to be started anew.
Keys 9-S: These are used to enter the secunty code and the
duress code.
OFF Key: When depressed subsequent to entry of the secunty
code. srlences alarms. memory. and trouble audibles and dis-
arms the system.
AWAY Key and LB0 (Red): When depressed subsequent to
entry of the security code, arms the entlre burglary system if
there are no faulted zones. The AWAY LED IS lit when the sys-
tem IS armed in this mode.
STAY Key end LED IRdl:
When depressed subseauenl to
entry of the security code, arms all of ihe non-interior'burglary
zones if there are no faulted zones. The STAY LED is kt when the
system IS armed in this mode.
CHK.BYP LEO (Yellow): This LED kghts steadily it a zone has
been bypassed by either force armtng or tndividual zone bypass-
mg. If flashes ii a trouble conditron has been detected. The latter
cpndrtron overrides the bypass mdication if both are present
srmultaneously.
BYPASS Key: When depressed subsequent lo entry 01 the
security code (either before or after armmg) and followed by one
or more zone numbers (1 to 6). will individually bypass the
zone(s) designated [assuming that the programming of the sys-
tem permits the bypassing of the particular zone(s)].
When depressed subsequent to entry of the security code and
either the AWAY or STAY keys. the burglary system will arm with
any faulted zones bypassed iassumingthat the programming of
the eyetern permits lhe bypessing of the perticulrr zone(s)].
INSTANT Key: When depressed subsequenr to entry of the
security code and either the AWAY or STAY keys, the burglary
system will arm with the entry delay disabled on any zones
designated as entry/exit zones making them instant alarm zones
for subsequent entry. The entry delay is restored subsequent to
the system being turned off.
COOE Key: When depressed subsequent to entry of the secur-
ity code, will permit the immediate (within 5 seconds) entry of 1
of 7 diierent secondary user changeable 4 digit security codes.
The access codes are entered by first entering a digit 2-6 tol-
lowed by the 4 digit security code. Secondary codes 3-6 permit
the performance of all of the functions permitted by the PROM
programmed master code and secondary code 2. except
change of themselves to a new code or creatron of new secondary
codes. Repeating digits are permitted in code entries.
CHIME Key: When depressed subsequent to entry of the secu-
nty code during the disarmed state, will cause entry to a mode
where any fault in a zone PROM selected for chime enable will
cause a brief loud tone to be heard at each security console and
remote keypad. The mode can be turned oft by subsequent
reentry of the code and redepression of the CHIME key.
READY LEO (Green): This LED is lit whenever all zones are
intact (ready for arming) during the disarmed state. It is off at
other times.
ENTER Keys When depressed subsequent to security code and
function or mode entry, eliminates the 2 second keying entry
delay that exists prior lo acting on the function or mode request
(an optional entry).
2 Audible Signals
Syslem Tumed OFF or Feiiuw to Arm: Single brief buzz
System Anned AWAY:
Two brief buzzes
System Armd
STAY:
Three brief buzzes
Trouble:
Rapidly pulsing buzz for a trouble or for a loss of AC
power beyond the programmed time period.
Entry Warning:
Slowly pulsing buzz activated during the entry
delay period.
f-3
!/
,,
6