33. Zorn Restore Enable
Zones that are PROM selected as restore zones will allow the
bell/siren to sound more than once if the zone returns to normal
and fauns again after the bell/siren has timed out
AS shipped, the system has all zones set up as non-restore
zones. Non-restore means that once a zone has gone into alarm
during the armed period, subsequent fauns of that zone will not
bigger a new alarm. The zone is effectively "locked-out".
preventing multiple false alarms in the event of a 'Swinger".
34.~Alarm EounderPrlmmy
Communlator
D&y
Enable
The 'Exterior Sounder/Primary Communicator Delay" was
explained as option #2 previously. This PROM option is srmply
the choice of burglary zones for which exterior sounder and
primary communicator delay is desired.
Communlator
Optlonr:
1. Communhtor
En&la
The system may be PROM programmed to transmit any
combination of the following messages:
a. 0ponmoM
Roporb
A closing report, if enabled, will bs sent whenever the
system is put in the AWAY' mode. The STAY mode will
not generate a closing report.
*NOTE: If the system is armed in the AWAY mode and the
user opens and closes an entry/exit zone and then
keys security
code
plus AWAY (keying error). the
system will remain in the AWAY mode, but will not
transmit either an opening or a closing report.
b. Zone Bypow Repmta
If PROM enabled, the system will report all bypassed zones IO
the central station. These bypass reports will take place at the
following times.
1) Whenever a 24 hour zone is bypassed.
2) Controlled zones will report bypassing at the time of arming
unless they are bypassed after arming. for which an
immediate bypass report is produced.
3) When the zone bypass is removed, a bypass restore
message will be sent for 24 hour zones (controlled zones
will not send bypass restore reports as an open report
automatically signifies bypass restore for these zones).
c. Trouble ReporN
The system will transmit a trouble report, if PROM enabled,
whenever a trouble condition rs sensed in a zone selected tor
trouble. When the trouble condition has restored, a restore
message will be sent. The delay in sending the trouble and
restore messages is 0 or 16 seconds, dependent upon
whether that zone was selected for dialer delay.
2 16 Euond
Eacmdmy
Communlutor
Delay
A 16 second delay may be added prior to the communicator
triggering to reduce the possibility of false alarms. This timing
begins after any delay already provided by the Exterior
Sounder/Primary Communicator Delay option (described
previously). The trigger delay option might be chosen. for
example, on zones not utilizing the exterior sounder delay. In
other words, setected zones can have the exterior sounder
and communicator delayed, and others can have iusf the
communicator delayed, with instant sounding. In addition to
zones l-6, trigger delays are available for Closing reports.
3. Reporl to &con&y
Phone Number Onlr
The system allows for the various communfcatOr reports to be
divided between two central stations (or two receivers). This
option is chosen in some situations, where, for example. alf
alarms may be routed to a primary alarm receiver while non-
critical items, such as troubles or open and closing reports,
might be routed to a secondary receiver.
4. YbuUanuus
Comntmhtor
Opt&ma
rmMosaaguOnO~~l
As shipped. the system is set up with a feature that Qrves
alarm messages priority over trouble messages and other
non-alarm messages, when sending in a format other than
Ademco High Speed.
.
For example, if an alarm message for me primary receiver
occurs white the communicator is reporting bypass
conditions to the secondary receiver, the communicator
will abort the bypass reports.
It
will then call the primary receiver to report an alarm. After
the alarm has been reported. the communicator will resume
reporting the bypasses.
Optionally. the system may be made to finish all messages to
the active phone number before switching to the other phone
number.
b. Duress Youage
to 6econd Phone Number
When PROM selected. this option routes duress messages to
the secondary receiver.
c. AC Fall~VLuw
RaRwy to &cond
Phone Number
When PROM selected. this option routes AC Failure and
Restore, Low Battery. and Test reports to the secondary
receiver.
d. Low Battery Report Format Selecl
As shipped, when using Ademco High Speed Format. the
system will reporf Low Battery messages as follows:
ACCT 5555 5565 6 Low Battery
A PROM option is available that enables battery failure
reporting in a diierent manner (See Section on High Speed
Format). This format also allows battery restore reports to be
transmitted.
8. Dual Raport
When PROM selected. this option causes dl communicator
messages to be sent lo Eolh a primary receiver and a
secondary receiver.
1. MT by S's (Alternate by Pairs)
This option, when PROM selected, will cause the communica-
tor to alternate between the primary receiver and the second-
ary receiver white it is attempting to get through. It will first
make two attempts to the primary receiver, then two attempts
to the secondary receiver. and so on (for an unlimited number
of attempts) until it receives a kit
signal from one receiver.
5. Communhtor
Ruton
Rsport En&a
If it is desired to communicate zone restore. the reporting can be
PROM enabled for any such zone or zones.
6. Communicator
Chanml Adgnmont
?
Each alarm zone may be assigned a communicator channel.
How the zones are assigned to channels affects the types of
reports that will be sent. As an example, each zone could be
given a different communicator code for unique zone reporting.
Or the zones could be grouped by function with the fire
zone as Channel (or Code) 1, the silent panic zones as Channel
(or Code) 2. and the burglary zones as Channel (or Cods) 3 (this
would allow the system to be compatible with an existing central
station alarm code scheme).
NOTI? Assigning a zone to report as Channel (or Code) 0
disables that zone from making any calls.
7. Communkator
Formal
lndiiuaffy
selectable for primary and secondary telephone
numbers - Ademco Low Speed and/or Ademco High Speed.
SESCOA. Radionics, Radionics "Superfast" and Radionics
"BFSK".
5. SubscrIber ID Length
3 or 4 digit length selectable for various low speed formats.