0.3 mA
Figure 22 – Anode control
Please note that the water has to be heated to operational temperatures at least once
before the test above can be performed.
In order to replace the anode the following should be done:
• Close the cold water inlet.
• Connect a hose to the drain valve so the water from the water tank can run into the
nearest drain.
• Open a hot water tapping point (to avoid vacuum in the water tank).
• When the water level in the tank is below the anode, this can be removed for inspec-
tion and replacement.
Check and replacement of anode must only be performed by skilled personnel.