Modbus Process Data - Honeywell SmartDrive Compact User Manual

Table of Contents

Advertisement

Honeywell

9.12.1 Modbus process data

Process data is an address area for fieldbus control. Fieldbus control is active when
the value of parameter 2.1 (Control place) is 3 (=fieldbus). The contents of the proc-
ess data has been determined in the application. The following tables present the
process data contents in the GP Application.
ID
Modbus register
2101
32101, 42101
2102
32102, 42102
2103
32103, 42103
2104
32104, 42104
2105
32105, 42105
2106
32106, 42106
2107
32107, 42107
2108
32108, 42108
2109
32109, 42109
2110
32110, 42110
2111
32111, 42111
Table 9.3: Output process data
ID
Modbus register
2001
32001, 42001
2002
32002, 42002
2003
32003, 42003
2004
32004, 42004
2005
32005, 42005
2006
32006, 42006
2007
32007, 42007
2008
32008, 42008
2009
32009, 42009
2010
32010, 42010
2011
32011, 42011
Table 9.4: Input process data
Parameter Descriptions
Name
FB Status Word
FB General Status Word
FB Actual Speed
Motor freq.
Motor speed
Motor current
Motor torque
Motor power
Motor voltage
DC voltage
Active fault
Name
FB Control Word
FB General Control Word
FB Speed Reference
PI Control Reference
PI Actual value
-
-
-
-
-
-
Scale
Type
-
Binary coded
-
Binary coded
0,01
%
0,01
+/- Hz
1
+/- Rpm
0,01
A
0,1
+/- % (of nominal)
0,1
+/- % (of nominal)
0,1
V
1
V
-
Fault code
Scale
Type
-
Binary coded
-
Binary coded
0,01
%
0,01
%
0,01
%
-
-
-
-
-
-
-
-
-
-
-
-
9
67