9.11 EASY USAGE MENU (CONTROL PANEL: MENU PAR -> P9)
13.2 D
RIVE SETUP
With this parameter you can easily set up your drive for four different applica-
tions.
Note! This parameter is only visible when the Startup Wizard is active. The
startup wizard will start in first power-up. It can also be started as follows. See
the figures below.
NOTE! Running the startup wizard will always return all pa-
rameter settings to their factory defaults!
READY RUN
STOP
A LARM
REF
MON
PAR
FLT
1
Press STOP
for 5 seconds
in main menu
PERFORM THE SAME
4
PROCEDURE FOR PAR. 1.4,
MOTOR NOMINAL CURRENT
Figure 9.15: Startup wizard
Parameter Descriptions
Alternates
in the display
FAULT
READY RUN
STOP
REF
MON
PAR
FLT
2
Push to enter edit mode
ALARM
FAULT
READY RUN
REF
MON
PAR
rp m
FLT
3
Select motor
nominal speed
and push
to confirm.
PERFORM DRIVE SETUP,
5
PAR. 13.2, SEE NEXT PAGE
9
65
STOP
ALARM
FAULT