Fault Tracing - Honeywell SmartDrive Compact User Manual

Table of Contents

Advertisement

5
22

5. FAULT TRACING

When a fault is detected by the inverter control electronics, the drive is stopped and
the symbol F together with the ordinal number of the fault and the fault code appear
on the display in the following format, e.g:
F1 02
The fault can be reset by pressing the Stop button on the control keypad or via the I/
O terminal or fieldbus. The faults with time labels are stored in the Fault history menu
which can be browsed. The different fault codes, their causes and correcting actions
are presented in the table below.:
Fault
Fault name
code
1
Overcurrent
2
Overvoltage
3
Earth fault
8
System fault
9
Undervoltage
Table 5.1 : Fault codes
Fault Tracing
Fault code (02 = overvoltage)
Fault ordinal number (F1 = latest fault)
Possible cause
Inverter has detected too high a
current (>4*I
) in the motor cable:
N
• Sudden heavy load increase
• Short circuit in motor cables
• Unsuitable motor
The DC-link voltage has
exceeded the internal safety limit:
• Too short a deceleration time
• High overvoltage spikes in
mains
Current measurement has
detected extra leakage current at
start:
• Insulation failure in cables or
motor
• Component failure
• Faulty operation
The DC-link voltage has
exceeded the internal safety limit:
• Most probable cause: too low
a supply voltage
• Inverter internal fault
• Power outages
Honeywell
Correcting actions
Check loading.
Check motor size.
Check cables.
Increase the deceleration
time (P.4.3).
Check motor cables and
motor.
Reset the fault and restart.
Should the fault recur, con-
tact technical support.
In case of temporary supply
voltage break reset the fault
and restart the inverter.
Check the supply voltage. If
it is adequate, an internal
failure has occurred.
Contact technical support.

Advertisement

Table of Contents
loading

Table of Contents