ICP DAS USA I-7521 User Manual page 35

Table of Contents

Advertisement

NOTE: the text shown in the ellipse region is "i7188XC>" and will be
displayed for I-7521/I-7522 /I-7523 modules, but "i-7188XB>" will be
displayed for I-7522A/I-7524/I-7527 modules.
Step 3: Type "752n_c" (for I-7521/I-7522/I-7523) or "752n_b" (for
I-7522A/I-7524/ I-7527) and press the Enter key to execute the
752n_c.exe or 752n_b.exe file (Note: the INIT* pin should be
connected to the GND pin). The I-752N module will revert to the
factory default settings without changing the EEPROM data. The
factory default settings are as follows:
COM Port
Module Address = 00
Baud Rate
Checksum
CrLfmode
Data format = 1 start bit + 8 data bits + 1 stop bit (N, 8, 1)
Step 4: Refer to Sec. 3.1 and send commands to COM2 to read the
configuration for COM 2 or other ports. Some examples are as
follows:
(a) Send the command string $00M[0x0D] to retrieve the module
name and record it
(b) Send the command string $00A[0x0D] to retrieve the module
address and record it
I-7521/I-7522/I-7522A/I-7523/I-7524/I-7527 User's Manual,Ver2.5 Aug.2015
= 2
= 9600
= DISABLED
= 0 (0x0D)
Type 752n_c+Enter and then the
windows 7188xw can be closed.
35