6 Unlocking
To unlock the device, insert
a flat bladed screwdriver
into the release slot and
turn the remote indicator
anticlockwise to release, as
shown.
Specification
Operating
Temperature
-10°C to 55°C
Storage
Temperature
5°C to 30°C
Humidity
Up to 95% non-condensing
Supply
6x AA Alkaline (Panasonic LR6AD Powerline /
Varta 4006 Industrial)
CAUTION!
Fitting of an incorrect battery type invalidates the product certification and
may result in poor performance.
IP Rating
IP23
Operating
Frequency
868MHz
Output
Transmitter
Power
Auto adjusting 0 - 14 dB (0 - 25 mW)
Dimensions
113mm (Ø) 81mm (D)
Weight
0.40kg
Location
Type A: For indoor use
©2018 EMS Ltd. All rights reserved
7 Configuration
The device's loop address is configured within the menu structure
of the Radio Hub.
Refer
to
the
Instructions (Doc Ref: TSD115) for further information.
Regulatory Information
Manufacturer
Year of
manufacture
Certification
Certification body
CPR Certificate DOP
Approved to
European Union
directives
Page 2 of 2
Wireless
Remote
Indicator
Free to download from
www.emsgroup.co.uk
EMS Ltd. Technology House, Herne Bay, Kent,
CT6 8JZ, United Kingdom
See devices serial number label
10
0359
0359-CPR-00127
EN54-25:2008. Incorporating corrigenda September
2010 and March 2012. Fire detection and fire alarm
systems.
Part 25: Components using radio links.
EMS declares that the radio equipment type FireCell
Wireless RIM is in compliance with Directive
2014/53/EU. The full text of the EU declaration of
conformity is available at the following internet
address:
www.emsgroup.co.uk
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the
European Union. For proper recycling, return this
product to your local supplier upon purchase of
equivalent new equipment, or dispose of it at
designated collection points. For more information
see www.recyclethis.info
Dispose of your batteries in an environmentally
friendly
manner
according
regulations.
TSD116 Iss 3 05/09/2018
Programming
to
your
local