Document No. 563-066
Installation Instructions
November 2, 2015
Required Tools
• Phillips screwdrivers, sizes 1 and 2
• Medium and small flat-blade screwdrivers
• 1/16" hex key
• Medium-duty electric drill and 3/16-inch
(4.8 mm) drill bit
• Small level and tape measure
NOTE: Depending on the actual installation
(surface mounting) some of these tools
may not be required.
Binder Instructions
CAUTION:
Do not mount the WRS within 10 feet of
other RF devices such as microwave
ovens, Wi-Fi/802.11 access points, and so
on.
1.
Remove the plastic insulating strip between the
battery in the WRS battery holder (or insert the
battery) to power up the WRS.
NOTE:
Even though the WRS is powered, it
stays in a low-power sleep mode until
commissioned.
If the WRS has an LCD panel, the
displayed value does not change until
the WRS is bound to an RSX.
2. Bind WRS to associated RSX using optional
auto-binding cable (part number 563-207) or
HMI command.
NOTE:
Verify associated RSX is installed and
powered up before binding.
Binding Using Auto-Binding Cable
To bind your WRS to its associated RSX using the
optional auto-binding cable, follow these steps:
1.
Using the Auto-binding cable (563-207), plug
the connector labeled Room Sensor Port into
the RJ-11 port on the WRS.
2.
Plug the other cable connector into the RJ-11
port on the RSX.
3.
If the RSX indicator light does not immediately
turn solid yellow, power cycle the RSX to enter
binding mode.
When binding is successful, the indicator light on the
RSX turns solid yellow. When successful, remove
the auto-binding cable.
Page 2 of 4
Binding Using HMI Commands
To bind your WRS to its associated RSX using HMI
commands, follow these steps:
1.
Connect a PC cable (540-143) from a computer
to the RJ-11 port on the bottom of the WRS.
2.
Start a HyperTerminal session, log on (1200
baud, 8 data bits, no parity, 1 stop bit, no flow
control), and then press ENTER to display the
WRS prompt.
3.
At the WRS HMI prompt, type
BIND RSX a (where a = EUID of the RSX), and
then press ENTER.
When binding is successful, the LED on the RSX
turns solid yellow, and the WRS initiates a
communication check with the RSX to verify link
quality.
When successful, remove the computer cable from
the WRS. By default the HMI will time out after five
minutes. Remove and reinsert plug to reactivate.
For additional information on using HMI commands
to change the default configuration, troubleshoot
binding, placement or other diagnostics, see the
Wireless Room Sensor Solution User's Guide
(563-068).
Mounting Instructions
CAUTION:
If the WRS cannot communicate with its
RSX for an extended period of time due to
the RSX not being commissioned or the
RSX is out of range, remove the battery to
avoid excessive battery drain.
1.
Select a location for the WRS, following the
standard rules for room temperature sensor
placement.
Always mount the sensor vertically. Locate the
sensor as follows:
• No further than 100 feet (30 m) from the
RSX, ideally in a location where there are no
major RF obstructions (for example, metal or
concrete walls) between the two devices.
• Per design specifications, and local
regulations.
• Where the air circulates around it freely (not
in recessed areas or behind doors).
• Allow a minimum of 4 inches (10 cm) free
space above and below for the front cover
removal tool and to allow proper airflow.