Directional Earth-Fault Protection - ABB REG615 Product Manual

Generator and interconnection protection
Hide thumbs Also See for REG615:
Table of Contents

Advertisement

Generator and Interconnection Protection
REG615
Product version: 5.0 FP1
Table 35. Directional earth-fault protection (DEFxPDEF)
Characteristic
Operation accuracy
1)2)
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Operate time accuracy in inverse time mode
Suppression of harmonics
Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × I
1)
Set
nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Maximum
Start value = 2.5 × I
,
Start value multiples in range of 1.5...20
n
36
DEFLPDEF
DEFHPDEF
DEFHPDEF
Start value
I
= 2 × set
Fault
DEFLPDEF
Start value
I
= 2 × set
Fault
Value
Depending on the frequency of the measured current: f
Current:
±1.5% of the set value or ±0.002 × I
Voltage
±1.5% of the set value or ±0.002 × U
Phase angle:
±2°
Current:
±1.5% of the set value or ±0.002 × I
(at currents in the range of 0.1...10 × I
±5.0% of the set value
(at currents in the range of 10...40 × I
Voltage:
±1.5% of the set value or ±0.002 × U
Phase angle:
±2°
Minimum
Typical
42 ms
46 ms
58 ms
62 ms
Typically 40 ms
Typically 0.96
<30 ms
±1.0% of the set value or ±20 ms
±5.0% of the theoretical value or ±20 ms
RMS: No suppression
DFT: -50 dB at f = n × f
, where n = 2, 3, 4, 5,...
n
Peak-to-Peak: No suppression
1MRS758279 B
±2 Hz
n
n
n
n
)
n
)
n
n
Maximum
49 ms
66 ms
3)
, f
= 50 Hz, earth-fault current with
n
n
ABB