High-Speed Output Hso With Bio0007; Front Port Ethernet Interfaces; Irig-B; Degree Of Protection Of Flush-Mounted Protection Relay - ABB REG615 Product Manual

Generator and interconnection protection
Hide thumbs Also See for REG615:
Table of Contents

Advertisement

Generator and Interconnection Protection
REG615
Product version: 5.0 FP1
Table 15. High-speed output HSO with BIO0007
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time constant L/R <40 ms, at
48/110/220 V DC
Operate time
Reset
Table 16. Front port Ethernet interfaces
Ethernet interface
Front
Table 17. IRIG-B
Description
IRIG time code format
Isolation
Modulation
Logic level
Current consumption
Power consumption
1)
According to the 200-04 IRIG standard
Table 18. Degree of protection of flush-mounted protection relay
Description
Front side
Rear side, connection terminals
Table 19. Environmental conditions
Description
Operating temperature range
Short-time service temperature range
Relative humidity
Atmospheric pressure
Altitude
Transport and storage temperature range
1)
Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2)
For relays with an LC communication interface the maximum operating temperature is +70 ºC
28
Protocol
Cable
TCP/IP protocol
Standard Ethernet CAT 5 cable with RJ-45 connector
Value
250 V AC/DC
6 A
15 A
30 A
5 A/3 A/1 A
<1 ms
<20 ms, resistive load
Value
1)
B004, B005
500V 1 min
Unmodulated
5 V TTL
<4 mA
<20 mW
Value
IP 54
IP 20
Value
-25...+55ºC (continuous)
1)2)
-40...+85ºC (<16h)
<93%, non-condensing
86...106 kPa
Up to 2000 m
-40...+85ºC
1MRS758279 B
Data transfer rate
10 MBits/s