Harvia HPC(S)7U1H Owner's/Operator's Manual page 9

Hide thumbs Also See for HPC(S)7U1H:
Table of Contents

Advertisement

Available languages

Available languages

Main Electrical Panel
Note: Control panel and power unit must be installed in a dry
place; away from spa, pool or shower; not outdoors. A
receptacle shall not be installed inside the sauna room.
Load Center
Load center shall be supplied by
electrical contactor during field
wiring. Load center can be
located in other serviceable
places, as well as location
shown on this diagram.
Figure 5.
Minimum safety distances and sauna controls.
HPC(S)7U1H
4''
HPC(S)7U3H
100mm
HPC(S)9U1H
HPC(S)9U3H
Figure 6.
Installing the temperature sensor
Heater model
Input
kW
HPC(S)7U1H
6,8
HPC(S)9U1H
9,0
HPC(S)11U1H
10,5
HPC(S)7U3H
6,8
HPC(S)9U3H
9,0
HPC(S)11U3H
10,5
Table 3. Supply wires (from the power unit to the heater)
Control Panel
Power Unit
Voltage Ph Amperage
1-Group
2-Group
connection
connection
240
1
28,25
18,9
240
1
37,5
25
240
1
43,75
29,2
208
3
18,8
n/a
208
3
25
n/a
208
3
29,2
n/a
EN
4"
100mm
Heater
Sensor
HPC(S)7U1H
HPC(S)7U3H
C
HPC(S)9U1H
HPC(S)9U3H
HPC(S)11U1H
HPC(S)11U3H
A
A
min.
2,8''/70mm
SEAL TIGHT CONDUIT
90°C WIRE
HPC(S)11U1H
HPC(S)11U3H
Min. 90 °C Copper
Suitable control units
supply wire AWG No.
1-Group
2-Group
1-Group connection
connection
connection
10
12
CX30-U1-U3 /
CX45-U1-U3
8
10
CX45-U1-U3
6
8
CX45-U1-U3
12
n/a
CX30-U1-U3 /
CX45-U1-U3
10
n/a
CX30-U1-U3 /
CX45-U1-U3
8
n/a
CX30-U1-U3 /
CX45-U1-U3
A
B
C
inch mm inch mm inch mm
1,2
30
4
100
35
890
1,2
30
4
100
35
890
1,2
30
4
100
32,5 830
B
4''
100mm
2-Group connection
CX30-U1-U3 /
CX45-U1-U3
CX30-U1-U3 /
CX45-U1-U3
CX30-U1-U3 /
CX45-U1-U3
n/a
n/a
n/a
9