Ranging; Analog Output - Vout; Other Functions; Bargraph - AEMC 721 User Manual

Clamp-on harmonic meter
Table of Contents

Advertisement

5.1.1 Ranging

Auto Ranging is selected by default and selects the best range for the
digital display and for the analog bargraph.
Pushing the RANGE push button selects a fixed manual range: 60 Arms
first, and 600 Arms on the second push.
The digital display and the bargraph indicate the selected range. RANGE
is displayed at the top of the display indicating a manual range selection.
Selection is also confirmed with audible tone.
To sequence back to Auto Ranging, push and hold the RANGE push
button for approximately 3 seconds. The displayed RANGE indicator will
disappear, confirmed with an audible tone.
5.1.2 Analog Output – Vout
In the Current Measurement mode, the Analog Output Vout is always acti-
vated in A~ (see § 5.8) and the 10 mV/A (or 100 mV/A) signal is present
at the voltage terminals.

5.1.3 Other Functions

All others push-button functions relating to current may be accessed in A:
• THD (%THD, %DF, CF)
• HZ
• PEAK/SMOOTH
• MIN/MAX recording
These functions are described further in this manual (see p. 16-24).

5.1.4 Bargraph

Please note that the analog bargraph will continue to display RMS cur-
rent values while other measurement functions are displayed (e.g. %THD,
%DF, CF, Hz, Min/Max, Smooth, Peak). The bargraph ranges are 60 Arms
and 600 Arms.