Download  Print this page

Toshiba PCT001Z-E Instruction Manual page 9

Trace tool
Hide thumbs

Advertisement

Title
Content
Constant at the
F678
time of filtering
F740
Trace selection
F741
Trace cycle
Trace data1
F742
Trace data2
F743
F744
Trace data3
F745
Trace data4
*4 5, 6, and 7ms are set as 4ms.
*5 My Function monitors 1 through 4 at 46 through 49 cannot be specified with any
parameter between F742 and F745 (kinds of data to be acquired).
Table2 Parameter concerning trace functions
0:Deselect 1:At tripping 2:At triggering
0:4ms 1:20ms 2:100ms 3:1s 4:10s
00:Output frequency (Hz)
01:Frequency command value (Hz)
02:Output current (%)
03:Input voltage (%)
04:Output voltage (%)
05:Compensated frequency (Hz)
06:Speed feedback (real-time value) (Hz)
07:Speed feedback (1-second filter) (Hz)
08:Torque (%)
09:Torque command (%)
11:Torque current (%)
12:Exciting current (%)
13:PID feedback value (Hz)
14:Motor overload factor (OL2 data) (%)
15:Inverter overload factor (OL1 data) (%)
16:Regenerative braking resistance overload
factor (OLr data) (%)
17:Regenerative braking resistor load factor
(%ED) (%)
18:Input power (kW)
19:Output power (kW)
23:Option AI2 input (%)
24:RR/S4 input (%)
25:VI/II input (%)
26:RX input (%)
27:Option AI1 input (%)
28:FM output (%)
29:AM output (%)
34:Integral input power (kWhr)
35:Integral output power (kWhr)
46:My Function Monitor1
47:My Function Monitor2
48:My Function Monitor3
49:My Function Monitor4
Adjustment range
*4
4ms~100ms
*5
*5
*5
*5
Same as trace data1
Same as trace data1
Same as trace data1
7
E6581478
Default
setting
64
1
2
0
1
2
3

Advertisement

Table of Contents
loading

  Related Manuals for Toshiba PCT001Z-E

This manual is also suitable for:

Tosvert vf-ps1Tosvert vf-as1