CL1XY4-DT1B2
CC-Link/LT Remote I/O Module
Please read this manual thoroughly before starting to use the product and
handle the product properly.
User's Manual
MODEL
CL1XY4-DT1B2
MANUAL Number
JY997D05601E
Date
September 2008
●SAFETY PRECAUTIONS●
(Read these precautions before using)
Please read this manual carefully and pay special attention to safely in order
to handle this product properly. Also pay careful attention to safely and handle
the module properly.
These precautions apply only to Mitsubishi equipment. Refer to the user's
manual of the CPU module to use for a description of the PLC system safety
precautions.
These ●SAFETY PRECAUTIONS● classify the safety precautions into two
categories: "DANGER" and "CAUTION".
Procedures which may lead to a dangerous condition
and cause death or serious injury if not carried out
DANGER
properly.
Procedures which may lead to a dangerous condition
and cause superficial to medium injury, or physical
CAUTION
damage only, if not carried out properly.
CAUTION
Depending on circumstances, procedures indicated by
may also be linked to serious results.
In any case, it is important to follow the directions for usage.
Store this manual in a safe place so that you can take it out and read it
whenever necessary. Always forward it to the end user.
[DESIGN PRECAUTIONS]
DANGER
• Configure an interlock circuit in a sequence program so that the system
operates on the safety side using the communication status information
in the event the data link falls into a communication problem.
Otherwise, erroneous output and malfunction may result in accidents.
• Remote input and output can not be switched ON or OFF when a
problem occurs in the remote I/O modules. Therefore build an external
monitoring circuit that will monitor any input signals that could cause a
serious accident.
CAUTION
• Do not have control cables and communication cables bundled with or
placed near by the main circuit and/or power cables. Wire those cables
at least 100mm(3.94 inch) away from the main circuit and/or power
cables. It may cause malfunction due to noise interference.
• Use the module and the flat cable dedicated to CC-Link/LT without
applying any force on them.
Otherwise, such cables may be broken or fail.
[INSTALLATION PRECAUTIONS]
CAUTION
• Use the module in an environment that meets the general specifications
contained in this manual. Using this module in an environment outside
the range of the general specifications could result in electric shock, fire,
erroneous operation, and damage to or deterioration of the product.
• Do not directly touch the module's conductive parts.Doing so could
cause malfunction or trouble in the module.
• Tighten the module securely using DIN rail or installation screws within
the specified torque range.
If the screws are too lose, the module may drop from its installation
position, short circuit, or malfunction. If the screws are too tight, the
screws may be damaged, which may cause the module to drop from its
installation position or short circuit.
• Install the module on a flat surface.
If the mounting surface has concave and/or convex, an excessive force
may be applied on the module, and nonconformity may be caused.
[WIRING PRECAUTIONS]
DANGER
• Perform installation and wiring after disconnecting the power supply at all
phases externally. If the power is not disconnected at all phases an electric
shock or product damage may result.
CAUTION
• Terminal screws which are not to be used must be tightened always.
Otherwise there will be a danger of short circuit against the bare solderless
terminals.
• Do not perform wiring to an idle terminal "NC" outside the product.
The product may be damaged by such external wiring.
• Perform correct wiring for the module according to the product's rated voltage
and terminal arrangement. Connecting to a power supply different from rating
or miss-wiring may cause fire, product failure or malfunction.
• Fix terminal screws securely within the regulated torque. Loose terminal
screws may cause fire and/or malfunction.
If the terminal screws are too tight, it may cause short circuit or erroneous
operation due to damage of the screws.
• Make sure foreign objects do not get inside the module, such as dirt and wire
chips. It may cause fire, product failure or malfunction.
• Attach a warning label (hazard symbol 417-IEC-5036) concerning the electric
shock to the location.
[STARTING AND MAINTENANCE PRECAUTIONS]
DANGER
• Do not touch the terminals when the power is ON. It may cause an electric
shock or malfunction.
• Perform cleaning the module or retightening of terminal screws after turning
OFF the all external power supply for sure. Failure to do so may cause failure
or malfunction of the modules
CAUTION
• Do not disassemble or modify the module. Doing so may cause failure,
malfunction, injury, or fire.
• The module case is made of resin; do not drop it or subject it to strong shock.
A module damage may result.
• Make sure to switch all phases of the external power supply OFF before
installing or removing the module to/from the panel. Failure to do so may
cause failure or malfunction of the modules.
[DISPOSAL PRECAUTIONS]
DANGER
• When disposing of this product, treat it as industrial waste.
[TRANSPORTATION AND MAINTENANCE PRECAUTIONS]
CAUTION
• During transportation avoid any impact as the module is a precision
instrument. Doing so could cause trouble in the module.
• If is necessary to check the operation of module after transportation, in case
of any impact damage.
●Notification of CE marking●
This notification does not guarantee that an entire mechanical module produced
in accordance with the contents of the notification comply with the following
standards. Compliance to EMC standards of the entire mechanical module
should be checked by the user / manufacturer.
Standards with which this product complies
Type : Programmable Controller (Open Type Equipment) Remote I/O module
Models : Products manufactured:
from February 1st, 2003 to April 30th, 2006 are compliant with
EN61000-6-4 and EN61131-2:1994+A11:1996+A12:2000
after May 1st, 2006 are compliant with EN61131-2:2003
Electromagnetic Compatibility
Remark
Standards (EMC)
EN61000-6-4:2001
Compliance with all relevant aspects of
Electromagnetic compatibility
the standard.
-Generic standards - Emission
(Radiated Emissions and Mains Terminal
standard for Industrial environment
Voltage Emissions)
Compliance with all relevant aspects of
EN61131-2:1994/A11:1996/A12:2000
the standard.
Programmable controllers
(RF Immunity, Fast transients, ESD and
-Equipment requirements and tests
Damped oscillatory wave)
Compliance with all relevant aspects of
the standard.
EN61131-2: 2003
(Radiated Emissions, Mains Terminal
Programmable controllers
Voltage Emissions, RF immunity, Fast
-Equipment requirements and tests
Transients, ESD, Surge, Voltage drops
and interruptions, Conducted and Power
magnetic fields)
For more details please contact the local Mitsubishi Electric sales site.
- Notes For compliance to EMC regulation.
It is necessary to install the CL1 series module in a shielded metal control panel.
1.
Outline of Product
This product is a terminal block type
composite I/O module connected to
CC-Link/LT.
This product has four input points (24
PW L RUN L
ERR.
VDC) and four output points (transistor
output).
2.
Name and Setting of Each Part and Terminal Arrangement
0 1
0 1
DIP switch
Input operation
Output operation
DIP switch assignment
indicator LEDs
indicator LEDs
40 20 10 8 4 2 1
HLD
Input/output is ON: Lit
ON
Status indicator
Input/output is OFF
LEDs
Connector for
PW
L RUN L ERR.
0 1
0 1
CC-Link/LT interface
CL1XY4-DT1B2
ON
Connector terminal
assignment
IN
40 2010 8 4 2 1
OUT
4
24G
3
DB
X0
2
DA
X1
1
+24V
LINK/PW
Y0
Y1
2-φ4.5 mounting hole
Terminal block for I/O interface
(M4 mounting screw)
Hook for installation to DIN rail
Terminal arrangement (Terminal number and Signal name)
1
3
5
7
9
11
13
DC
X0
X0
X1
X1
NC
NC
NC
Y0
Y1
Y1
DC24A
24A
X0
X1
NC
NC
Y0
Y1
Orange color
2
4
6
8
10
12
DC
X0
X1
COMB
NC
NC
NC
COM+
Y1
COM+
DC24B
24B
COMB
COMB
NC
NC
COM+
COM+
Name
Description
PW
ON while the power is supplied.
L RUN ON while normal operation is executed.
ON:When a communication error or DIP switch
setting error occurred
Flickering at a constant interval:
Status indicator
When the setting of the DIP switch was changed
while the power was supplied (even while the LED is
LEDs
L ERR.
flickering, the operation continues. The new setting
becomes valid when the power is turned OFF once,
then ON again.)
Flickering at a intermittent interval:
When a terminal resistor is not attached or when the
module or a connection cable is affected by noise
ON while the input or output
0 1
is ON. Extinguished while
I/O operation
the input or output is OFF.
indicator LEDs
Input operation
Output operation
indicator
Connector for CC-
Connector for CC-Link/LT communication line/module power
Link/LT interface
supply (24G/DB/DA/+24V)
Terminal block
Terminal block to connect input signals, output signals, I/O
for I/O interface
power supply and load power supply
Set the 10's digit of the station No. using "STATION NO. 10",
"STATION NO. 20" and "STATION NO. 40". Set the 1's digit of
the station No. using "STATION NO. 1", "STATION NO. 2",
"STATION NO. 4" and "STATION NO. 8".
Factory default = All bits are OFF.
Make sure to set the station No. in the range from 1 to 64.
If any station No. outside the range from 1 to 64 is set, it is
Station number
regarded as an error and the L ERR. LED lights.
setting switches
Example: When setting the station No. to "32", set the
DIP switch as follows.
10's digit
1's digit
Station
No.
40
20
10
8
4
32
OFF
ON
ON
OFF
OFF
Name
Description
Holds the output (when an error has occurred).
Response time
HLD
ON: Holds the output.
setting switch
OFF: Clears the output.
0 1 2
3
3.
Installation
ON
IN
STATION NO.
The CL1XY4-DT1B2 can be installed to DIN rail or directly installed using
X0
X1
X2
mounting screws.
X3
Each installation procedure is described below.
3.1 Installation to DIN rail
Align the upper DIN rail installation groove in the module with the DIN rail
1), and press the module in that status 2).
When removing the module, pull the hook downward for installation to DIN
rail 3), then remove the module 4).
DIN rail mounting screw pitch
: Extinguished
When installing the module to the DIN rail, tighten the mounting screws at
the pitch of 200mm(7.87") or less.
Installation
1)
2)
15
DC
Applicable DIN rail TH35-7.5Fe and TH35-7.5AI
DC24V
24V
14
16
DC
3.2 Direct installation
DC24G
24G
Screw-tighten the module by attaching M4 screws to the upper and lower
mounting holes (two holes in all) provided in the module.
Install the module so that the clearance of 1 to 2mm (0.04" to 0.08") is
assured for each module.
×
×
M4
0.7mm(0.03")
16mm(0.63") or more
Applicable screw
(Tightening torque range: 78 to 108 N⋅cm)
4.
Wiring
4.1 External wiring
The input terminals of the CL1XY4-DT1B2 can be wired as positive
common or negative common depending on the used sensor. (The output
wiring is fixed to the sink output.)
Positive common
0 1
CL1XY4-DT1B2
Connector for
CC-Link/LT
interface
1 +24V
External power
indicator
2 DA
supply of the
3 DB
input part
4 24G
(24V DC)
Terminal block for I/O interface (positive common input)
1
DC24A
2
DC24B
R
3
X0
4
COMB
5
X1
6
COMB
7
NC
8
NC
Terminal block for I/O interface (sink output)
9 NC
10
NC
L
11
Y0
12
COM+
L
13
Y1
14
COM+
Load
15
DC24V
power
16
DC24G
supply
2
1
ON
OFF
Removal
4)
3)
Isolation
DC DC
R

Advertisement

loading

Summary of Contents for Mitsubishi CL1XY4-DT1B2

  • Page 1 STATION NO. The CL1XY4-DT1B2 can be installed to DIN rail or directly installed using • Terminal screws which are not to be used must be tightened always. Please read this manual thoroughly before starting to use the product and mounting screws.
  • Page 2 Max. load current 0.1A/point, 0.4A/1common Mitsubishi will not be held liable for damage caused by factors found not to be the Bleeder resistor *1 cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi Operating Max.
  • Page 3 Storage ambient Warranty -25 to 75°C (-13 to 167°F) temperature Mitsubishi will not be held liable for damage caused by factors found not to be the Max. load current 0.1A/point, 0.4A/1common Bleeder resistor *1 cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi Operating Max.