Commissioning The Transmitter; Figure 31: Connections Required To Validate Communication In A Non-Hazardous Area - ABB 266 MODBUS User Manual

2600t series pressure transmitters
Hide thumbs Also See for 266 MODBUS:
Table of Contents

Advertisement

4 Transmitter start up

Commissioning the transmitter

Once the transmitter has been installed, powered, and configured, commission the transmitter into operation.
The following are requirements to commission the transmitter.
— Validate communication
— Leak-test the connections
— Validate the transmitter measurement
— Put the transmitter in service
Validating communication
®
The correct procedure for validating communication is based on the usage application. The 266 MODBUS
multivariable is
®
designed to be backward compatible with existing 267/269CS installations. In applications where the 266 MODBUS
device is
®
replacing an existing unit, simply transfer the wiring from the existing unit to the 266 MODBUS
device. Using any of the
®
®
methods listed in section 4.3.1.1, Set MODBUS
device address, set the MODBUS
address to the same address as the device
being replaced and communication should immediately be available. No further action is required.
In new installations, setup and validation can still be a simple task if the communication and supply voltage wiring meets the
requirements of the device (Figure 31). Once the wiring has been established, communication validation is simply sending a
®
request to the device and receiving the response. Any of the Read registers listed in the MODBUS
register map can be used
®
for the validation process. See section Appendix C, MODBUS
register lists (page 86), for information about communication
packet structures and host timing.

Figure 31: Connections required to validate communication in a non-hazardous area

266 MODBUS® multivariable transmitter User manual 2105216 Rev. AB | 37

Advertisement

Table of Contents
loading

Table of Contents