ABB 266 MODBUS User Manual page 98

2600t series pressure transmitters
Hide thumbs Also See for 266 MODBUS:
Table of Contents

Advertisement

Register Address
Data
Type
32 bit
16 bit
5561
5081–5082
F
5562
5083–5084
F
5563
5085–5086
F
5564
5087–5088
F
5565
5089- 5090
F
5566
5091- 5092
F
5567
5093-5094
F
5568
5095-5096
F
5569
5097-5098
F
5570
5099-5100
F
5571
5101-5102
F
5572
5103-5104
F
5573
5105-5106
F
5574
5107-5108
F
5575
5109-5110
F
5111 – 5112
5576
F
5113 – 5114
5577
F
5115 – 5116
5578
F
5579
5117
x
5580
5118
x
64001
64001
U8
64002-
64002
U32
64003
90 | 266 MODBUS® multivariable transmitter User manual 2105216 Rev. AB
Object description
Transducer Temperature Maximum ever measured value
Transducer Temperature Minimum ever measured value
RTD Maximum ever measured value
RTD Minimum ever measured value
Customer Operating Range Alarm Levels
DP Above URV Alarm Set at this level (in DP units) referenced to register 5541
='s URV + ((URV-LRV) * DPHysteresis * 0.01 )
DP Below LRV Alarm Set at this level (in DP units) referenced to register 5542
='s LRV - ((URV-LRV) * DPHysteresis * 0.01)
DP Below URV Alarm Clears at this level (in DP units) referenced to register 5541
='s URV - ((URV-LRV) * DPHysteresis * 0.01 / 2)
DP Above LRV Alarm Clears at this level (in DP Units) referenced to register 5542
='s LRV + ((URV-LRV) * DPHysteresis * 0.01 / 2)
DP Alarm Hysteresis Percent of User Range Span referenced to register 5541 &
5542 (default 2%)
(DPHysteresis)
SP Alarm Hysteresis Percent of User Range Span referenced to register 5543 &
5544 (default 2%)
(SPHysteresis)
SP Above URV Alarm Set at this level (in SP units) referenced to register 5543
='s URV + ((URV-LRV) * SPHysteresis * 0.01 )
SP Below LRV Alarm Set at this level (in SP units) referenced to register 5544
='s URV - ((URV-LRV) * SPHysteresis * 0.01 )
SP Below URV Alarm Clears at this level (in SP units) referenced to register 5543
='s LRV - ((URV-LRV) * SPHysteresis * 0.01 / 2)
SP Above LRV Alarm Clears at this level (in Sp Units) referenced to register 5544
='s LRV + ((URV-LRV) * SPHysteresis * 0.01 / 2)
Measurements Bias Parameters
DP bias value is being added to the DP measurement producing an overall offset
adjustment.
SP bias, see preceding register for discussion.
Set DP to a value, units are same as the DP measurement.
DP bias = value – current measurement.
This results in the reported value in register 401-402 to be the value.
Set SP to value, see preceding register for discussion.
Reset DP Bias, sets the bias value to zero, effectively removing any effects of bias
on DP measurement.
This is an action register and the data value has no meaning.
Reset SP Bias, sets the bias value to zero, see preceding register.
Informative / Maintenance (Available in all Modbus mapping modes)
Modbus mapping selection:
0 = ABB map
1 = Rosemont map
2 = Invensys map
Date and time the CB firmware was built. Julian date number of seconds since Jan
01, 1970 00:00:00