Register Address
Type
32 bit
16 bit
* Means these are ROM constant defaults and a read will always return these values.
U8
7060
60
7061
61
U8
7062
62
U8
7131
131
U8
† Value selected using HMI must equal one of these specific measurement units, or a NAK will be returned.
401 – 402
7401
F
403 – 404
7402
F
405 – 406
7403
F
407 – 408
7404
U32
409 – 410
7405
U32
411 – 412
7406
U32
413 – 414
7407
F
415 – 416
7408
F
417 – 418
7409
F
419 – 420
7410
F
421 – 422
7411
F
423 – 424
7412
F
425 – 426
7413
F
427 – 428
7414
F
429 – 430
7415
F
431 – 432
7416
F
433 – 434
7417
F
435 – 436
7418
F
437 – 438
7419
F
439 – 440
7420
F
441 – 442
7421
F
443 – 444
7422
F
445 – 446
7423
F
447 – 448
7424
F
449 – 450
7425
F
451 – 452
7426
F
453 – 454
7427
F
*Constant /
Object description
Default
Differential Pressure units select code
1 inch of water at 60 °F (ROM default)
2 Pascal
3 Kilopascals
6 inches of water at 68 °F
Static Pressure units select code
3 Kilopascal
4 Megapascal
5 PSIA (ROM default)
Temperature units select code
20 Degree Celsius
21 Degree Fahrenheit (ROM default)
Modbus turn-around response delay (ms per count)
Differential Pressure (Damping, Calibration and Units applied) floating point, 401 is
high word, 402 is low word.
Static Pressure (Damping, Calibration and Units applied) floating point, 401 is high
word, 402 is low word.
Process Temperature (Damping, Calibration and Units applied) floating point, 401 is
high word, 402 is low word.
This may be external RTD or sensor value depending on configuration.
Diagnostics Status Word 1 and 2
Diagnostics Status Word 3 and 4
Diagnostics Status Word 5 and 6
DP URL, Upper Range Limit (Set by Measurement Sensor)
DP LRL, Lower Range Limit (Set by Measurement Sensor)
DP URV, Operating Upper Range Value (default URL)
DP LRV, Operating Lower Range Value (default LRL)
SP URL, Upper Range Limit (Set by Measurement Sensor)
SP LRL, Lower Range Limit (Set by Measurement Sensor)
SP URV, Operating Upper Limit (default SP URL)
SP LRV, Operating Lower Limit (default SP LRL)
T URL, Upper Range Limit (default 850ºC)
T LRL, Lower Range Limit(default -200ºC)
T URV, Operating Upper Range Value (default URL)
T LRV, Operating Lower Range Value (default LRL)
DP offset calibration value (default 0.0)
DP span calibration value ( default URL)
DP damping (default 0.0)
SP offset calibration value (default 0.0)
SP span calibration value ( default URL)
SP damping (default 0.0)
T offset calibration value (default 0.0)
T span calibration value (default URL)
T dampening (default 0.0)
Appendix C MODBUS® register lists