ABB 266 MODBUS User Manual page 20

2600t series pressure transmitters
Hide thumbs Also See for 266 MODBUS:
Table of Contents

Advertisement

2 System description
®
MODBUS
communication can be configured to emulate three different transmitter register maps:
— ABB transmitter 267/269 (Default)
— Rosemount 3095FB
— Invensys IMV25
®
®
Go to Appendix C, MODBUS
register lists for detailed MODBUS
register tables.
®
Mapping tables assign 16 bit system objects to 32 bit register addresses. This allows the MODBUS
Master to select and use a
®
single addressing mode. The MODBUS
processor zero-fills any undefined 16 bit objects. The defined bits occupy the LSB
(least significant (lower) bits) and the zeroed bits are the MSB (most significant (higher) bits). A 32 bit register address is
®
mapped the same way as a single 16 bit register address. MODBUS
communication prevents a protected register object from
being overwritten.