2 Installation and connection

2-3 Connecting the AC input

2-3 Connecting the AC input
1.
When you connect it to a commercial power source, battery charging automatically
starts regardless of the ON/OFF state of the "Power" Switch and charging completes
within 8 hours.
100VAC (Example of connection)
Load
To reduce the risk of fire,
● Connect only to a circuit provided with 15A maximum branch circuit overcurrent
protection in accordance with the National Electric Code, ANSI/NFPA 70 and the
Canadian Electrical Code, Part I, C22.1.
For Pluggable Equipment – The socket-outlet shall be installed near the equipment
and shall be easily accessible.
● Provide an emergency stop switch or an externally-installed breaker on the external
output side.
Reference
● The unit was charged before shipment, but it may have self-discharged during shipment,
resulting in a reduced backup time. We recommend charging the unit before use.
● You can perform "3-2 Checking the operation " also before charging the battery.
When installation and connection are complete, connect the unit's AC input plug to a
commercial power source.
Make sure to connect the AC input of the unit into a wall outlet
(commercial power source) with rated input voltage of 100/110/115/120V
AC.
● Connecting to a wall outlet (commercial power source) of a different rated voltage
may result in fire.
● The unit may fail.
For other cautions when connecting the UPS, refer to "Caution (for installation and
connection)" shown in the "Safety precautions" of the beginning of this manual.
Installation and connection is now complete.
36
Isolator switch or circuit breaker
Caution
* When in use, make sure the terminal block
cover is attached.
AC input plug
Commercial
power source
BU100RS