3 Check and start operation
3-4 Interpreting beeps and displays
(2) When "Power" switch is "OFF"
Status
No.
indicator
34
35
36

3-4-5 Display and beep for battery replacement

37
38
39
54
Power
Battery
Battery
supply
replace
mode
Beep
output
ment
LED
LED
LED
Continuous
Continuous
Continuous
Intermittent
2.0-second
intervals
Intermittent
2-second
intervals
---
---
---
None
Charging
Description
Failure occurred. When
the "Buzzer
OFF
Pause/Test" switch is
pressed, the details of
the error are displayed.
Stopped charging due
OFF
to abnormal rise in
battery charge voltage.
Stopped charging due
OFF
to abnormal drop in
battery charge voltage.
The self-diagnosis test
detected a weak battery
ON
(warning only, output
continues).
Battery life counter went
ON
off-scale. (Warning only.
Outputs continue.)
Battery life counter has
OFF
been reset.
Solution
There is a problem with
the unit. Contact the
shop of purchase or the
OMRON Electronic
Systems & Equipments
Customer Support
Center.
Turn off AC input.
(Same as above.)
Replace the battery.
You can replace the
weak battery with a
separately purchased
replacement battery as
needed.
See also "4-2 Replacing
the battery".
Be sure to reset the
battery life counter after
replacing the battery.
See also "4-2 Replacing
the battery".