2.3.5

Protruding the heat sink through a panel

When encasing an inverter to an enclosure, the heat generated in the enclosure can be greatly reduced by protruding the
heat sink of the inverter.
When installing the inverter in a compact enclosure, etc., this installation method is recommended.
 Panel cutting
Cut the panel of the enclosure according to the inverter capacity.
FR-F842-07700(355K)
FR-F842-08660(400K)
200
520
6-M10 screw
200
Hole
(Unit: mm)
Installation of the inverter and enclosure design
FR-F842-09620(450K)
FR-F842-10940(500K)
FR-F842-12120(560K)
660
240
Hole
INSTALLATION AND WIRING
6-M10 screw
240
(Unit: mm)